386 Set up with the display and adjustment moduleVEGAPULS 61 • Foundation Fieldbus41716-EN-160224This menu item is used to select the national language for further pa-rameter adjustment. You can change the selection via the menu item"Setup - Display, Menu language".With the "OK" key you move to the main menu.6.4 Parameter adjustmentThe instrument is adapted to the application conditions via the pa-rameter adjustment. The parameter adjustment is carried out with anadjustment menu.The main menu is divided into five sections with the following func-tions:Setup: Settings, for example, for medium, application, vessel, adjust-ment, dampingDisplay: Language setting, settings for the measured value indicationas well as lightingDiagnosis: Information, e.g. on instrument status, pointer, measure-ment certainty, simulation, echo curveFurther settings: e.g. instrument units, unit SV 2, false signal sup-pression, linearization, date/time, reset, copy sensor dataInfo: Instrument name, hardware and software version, date of manu-facture, device ID, instrument featuresIn the main menu item "Setup", the individual submenu itemsshould be selected one after the other and provided with the correctparameters to ensure optimum adjustment of the measurement. Theprocedure is described in the following.SetupEach medium has different reflection properties. With liquids, furtherinterfering factors are fluctuation product surface and foam genera-tion. With bulk solids, these are dust generation, material cone andadditional echoes from the vessel wall.To adapt the sensor to these different measuring conditions, theselection "Liquid" or "Bulk solid" should be made in this menu item.Selection of nationallanguageMain menuSetup - Medium