579 Diagnosis, asset management and serviceVEGAPULS 64 • HART and accumulator pack56611-EN-180115CodeText messageCause Rectification DevSpecState in CMD 48F125Impermissible elec-tronics temperature• Temperature of the electronicsin the non-specified range • Check ambient temperature• Insulate electronics• Use instrument with highertemperature rangeBit 7 of Byte 0 … 5F260Error in the cali-bration• Error in the calibration carriedout in the factory• Error in the EEPROM• Exchanging the electronics• Send instrument for repairBit 8 of Byte 0 … 5F261Error in the instru-ment settings• Error during setup• False signal suppression faulty• Error when carrying out a reset• Repeat setup• Carry out a resetBit 9 of Byte 0 … 5F264Installation/Setuperror• Adjustment not within the vesselheight/measuring range• Max. measuring range of theinstrument not sufficient• Check or correct installationand/or parameter settings• Use an instrument with biggermeasuring rangeBit 10 of Byte 0 … 5F265Measurement func-tion disturbed• Sensor no longer carries out ameasurement• Operating voltage too low• Check operating voltage• Carry out a reset• Disconnect operating voltagebrieflyBit 11 of Byte 0 … 5The following table shows the error codes and text messages in thestatus message "Function check" and provides information on causesas well as corrective measures.CodeText messageCause Rectification DevSpecState in CMD 48C700Simulation active• A simulation is active • Finish simulation• Wait for the automatic end after60 mins."Simulation Active"in "StandardizedStatus 0"The following table shows the error codes and text messages in thestatus message "Out of specification" and provides information oncauses as well as corrective measures.CodeText messageCause Rectification DevSpecState in CMD 48S600Impermissible elec-tronics temperature• Temperature of the electronicsin the non-specified range • Check ambient temperature• Insulate electronics• Use instrument with highertemperature rangeBit 8 ofByte 14 … 24S601Overfilling• Danger of vessel overfilling • Make sure that there is nofurther filling• Check level in the vesselBit 9 ofByte 14 … 24S603Impermissible oper-ating voltage• Operating voltage below speci-fied range • Check electrical connection• If necessary, increase operatingvoltageBit 11 ofByte 14 … 24Function checkOut of specification