7010 SupplementVEGAPULS 65 • Modbus and Levelmaster protocol41365-EN-160224Parameter Length Code/DataList of Object length 1 ByteList of Object value 1 Byte Depending on the Object ID10.5 Levelmaster commandsThe VEGAPULS 65 is also suitable for connection to the following RTUs with Levelmaster protocol.The Levelmaster protocol is often called "Siemens" "Tank protocol".RTU ProtocolABB Totalflow LevelmasterKimray DACC 2000/3000 LevelmasterThermo Electron Autopilot LevelmasterParameters for the bus communicationThe VEGAPULS 65 is preset with the default values:Parameter Configurable Values Default ValueBaud Rate 1200, 2400, 4800, 9600, 19200 9600Start Bits 1 1Data Bits 7, 8 8Parity None, Odd, Even NoneStop Bits 1, 2 1Address range Levelmaster 32 32The Levelmaster commands are based on the following syntax:• Capital letters are at the beginning of certain data fields• Small letters stand for data fields• All commands are terminated with "" (carriage return)• All commands start with "Uuu", whereby "uu" stands for the address (00-31)• "*" can be used as a joker for any position in the address. The sensor always converts this inits address. In case of more than one sensor, the joker must not be used, because otherwiseseveral slaves will answer• Commands that modify the instrument return the command with "OK“. "EE-ERROR" replaces"OK" if there was a problem changing the configurationReport Level (and Temperature)Request:Parameter Length Code/DataReport Level (and Temperature) 4 characters ASCII Uuu?