104 Connecting to the bus systemVEGAPULS 61 • Profibus PA47106-EN-1611044 Connecting to the bus system4.1 ConnectingThe voltage supply and signal output are connected via the spring-loaded terminals in the housing.Connection to the display and adjustment module or to the interfaceadapter is carried out via contact pins in the housing.Information:The terminal block is pluggable and can be removed from theelectronics. To do this, lift the terminal block with a small screwdriverand pull it out. When reinserting the terminal block, you should hear itsnap in.Proceed as follows:1. Unscrew the housing lid2. If a display and adjustment module is installed, remove it by turn-ing it slightly to the left.3. Loosen compression nut of the cable gland and remove blindplug4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.1 cm (0.4 in) of insulation from the ends of the individual wires5. Insert the cable into the sensor through the cable entryFig. 6: Connection steps 5 and 6 - Single chamber housingConnection technologyConnection procedure