WAGO-I/O-SYSTEM 750 Commissioning 95750-843 ETHERNET Controller 10 MBitManualVersion 1.2.0Pos : 78.15.18 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/BootP-T abelle editi eren - T eil 2 (Contr oller) @ 6\mod_1264498719375_21.doc x @ 48711 @ @ 1The examples shown contain the following information:Table 33: Information in the BootP tableInformation Descriptionnode1, node2 Any name for a node can be specified here.ht=1 Network hardware type indicated here. For ETHERNET the hardware type is1. These numbers are clarified RFC1700.ha=0030DE000100ha=0030DE000200Specify the hardware address (MAC ID) for the controllershere (hexadecimal).ip= 10.1.254.100ip= 10.1.254.200Specify the IP address for the controller here (decimal)T3=0A.01.FE.01 Specify the gateway IP address here (hexadecimal)sm=255.255.0.0 The subnet mask for the subnetwork to which the controllerbelongs can also be specified here (decimal).The local network that is described in this description does not require a gateway.You can therefore apply the example "Example of entry with no gateway" here.3. In the following text line, replace the 12-place hardware address locatedbehind “ha=” in this example.node1:ht=1:ha=0030DE000100:ip=10.1.254.1004. In place of this, enter the MAC address for your own controller.5. If you would like to specify a name for your fieldbus node, delete "node1"in the text and enter the node name you wish to use.node1:ht=1:ha=0030DE000100:ip=10.1.254.1006. To assign the controller a specific IP address, mark the IP address givenhere in the example after “ip=” and enter your own IP address.node1:ht=1:ha=0030DE000100:ip=10.1.254.1007. Since you do not need the second example "Example of entry with gateway"here, place the number sign (#) in front of the text line in Example 2 as acomment symbol:# node2:hat=1:ha=003 0DE 0002 00:ip=10.1.254.200:T3=0A.01.FE.01This line will not be evaluated after this.Enter addresses of other nodes in bootptap.txt!For addressing additional fieldbus nodes, enter a similar text line for each node,with your own specific data.8. In the menu File select the menu item Save to store the changed settings inthe "bootptab.txt" file.