114 Appendix WAGO-I/O-SYSTEM 750750-495 3-Phase Power Measurement ModuleManualVersion 1.0.0Table 63: Parameter 23Parameter 23 – Overvoltage threshold phase L1Function Data type Access Factory settingOvervoltage threshold phase L1,Resolution: 0.1 VUINT R/W 0x1004 (410 V)0: Overvoltage is not checked.≥1: Overvoltage threshold (value)Table 64: Parameter 24Parameter 24 – Overvoltage threshold phase L2Function Data type Access Factory settingOvervoltage threshold phase L2,Resolution: 0.1 VUINT R/W 0x1004 (410 V)0: Overvoltage is not checked.≥1: Overvoltage threshold (value)Table 65: Parameter 25Parameter 25 – Overvoltage threshold phase L3Function Data type Access Factory settingOvervoltage threshold phase L3,Resolution: 0.1 VUINT R/W 0x1004 (410 V)0: Overvoltage is not checked.≥1: Overvoltage threshold (value)Table 66: Parameter 26 and 27Parameter 26 und 27 – Overcurrent threshold phase L1Function Data type Access Factory settingOvercurrent threshold phase L1,Resolution: 0.1 mA UINT R/W 0x0000C350(5000 mA)0: Overcurrent is not checked.≥1: Overcurrent threshold (value)Table 67: Parameter 28 and 29Parameter 28 und 29 – Overcurrent threshold phase L2Function Data type Access Factory settingOvercurrent threshold phase L2,Resolution: 0.1 mAUINT R/W 0x0000C350(5000 mA)0: Overcurrent is not checked.≥1: Overcurrent threshold (value)