G 25 Operationwc_tx000137gb.fm 312.5 Current Overload FaultAlong with engine functions the ECM continuously monitors the currentload in each phase. The values for current overload are programmedinto the ECM at the factory and are different for each generator size.When an overload condition is sensed in any leg, the engine will shutdown and the LCD panel will display the fault condition shown above.Before restarting the generator, the cause of the overload should bedetermined and eliminated. Review all loads attached to the generatorand make sure they do not exceed the power rating of the unit.2.6 ApplicationThis heavy-duty, compact, sound-attenuated generator is designed toprovide single and three-phase power for construction, commercial,and industrial applications where reliable power is needed.NOTICE: Do not exceed the power output of the generator. Damageto tools or generator will occur. Refer to Technical Data.When using the generator as a stand-by or substitute power supply,make sure the voltage and phase rotation of the line connectionsmatch those of the utility lines or of any other power source normallyused. Failure to match phase rotation and voltage may causeequipment connected to the generator to operate incorrectly!This could create unsafe operating conditions.NOTICE: DO NOT exceed the rated current limit of any receptacle.Indicates that the engine speed dropped below55Hz (1650 rpm) for more than 15 secondsand the ECM has automatically shut down theengine.FAULTUNDERSPEED 53FAULTOVERLOAD