SYSTEM CONNECTIONS7-2 XEROX DOCUPRINT 96/4635/180 IPS INSTALLATION PLANNING GUIDECable locationsTo run the cables beneath the flooring effectively, it is necessary toknow where the cables enter and exit the printer. The followingdiagrams show those locations (marked with an X).All power cords attach to the back of the printer. Listed below are thedistances of the printer power cord attachments from the left end ofthe printer as you face it.Figure 7-1. 96/4635/180 cable enter/exit location (top view)• 180 power cord attachments—distance from end of printer:— Cord 1: 36 inches / 914 mm (with ELCI)— Cord 2: 23 inches / 584 mm (with ELCI)• 96 and 4635—distance from end of printer: 14 inches / 356 mmChannel attachmentsThe IPS printing system conforms to IBM standards andrequirements for any channel-attached printer. When you channel-attach your printer, keep the following in mind:• Channel length is usually determined by the length of thecables, the number of devices on the channel, and the numberof connections in the cable itself (for example, connecting twocables to each other).• Subtract 15 feet from the total allowable cable length for anydevice attached to the channel or for any connection of twocables.• IBM channel cable lengths are as follows:— Gray: 200 feet / 61 m (with one device, 185 feet / 56 m)— Blue: 400 feet / 122 m (with one device, 385 feet / 117 m)For further information regarding IBM channel connections, refer tothe following IBM manuals:• IBM System 360 and System 370 Input-output InterfaceChannel to Control Unit OEM Information (#GA22-6974-3825)• Page Printer Product Description (#G544-3482)• 3825 Introduction and Planning Guide (#G544-3480).BackFront14"/356 mmOperator areaPrinter withfeeder/stackermodules