6 Related Drive ParametersYASKAWA ELECTRIC SIEP C730600 59A V1000 Option Modbus TCP/IP Technical Manual 21F7-06(3EA)<5>Subnet Mask 2 Sets the static/fixed Subnet Mask.Parameter F7-06 sets the second most significant octet.Default: 255Range: 0 to 255F7-07(3EB)<5>Subnet Mask 3 Sets the static/fixed Subnet Mask.Parameter F7-07 sets the third most significant octet.Default: 255Range: 0 to 255F7-08(3EC)<5>Subnet Mask 4 Sets the static/fixed Subnet Mask.Parameter F7-08 sets the fourth most significant octet.Default: 0Range: 0 to 255F7-09(3ED)<5>Gateway Address 1 Sets the static/fixed Gateway address.Parameter F7-09 sets the most significant octet.Default: 192Range: 0 to 255F7-10(3EE)<5>Gateway Address 2 Sets the static/fixed Gateway address.Parameter F7-10 sets the second most significant octet.Default: 168Range: 0 to 255F7-11(3EF)<5>Gateway Address 3 Sets the static/fixed Gateway address.Parameter F7-11 sets the third most significant octet.Default: 1Range: 0 to 255F7-12(3E0)<5>Gateway Address 4 Sets the static/fixed Gateway address.Parameter F7-12 sets the fourth most significant octet.Default: 1Range: 0 to 255F7-13(3F1) Address Mode at StartupSelects how the option address is set.0: Static1: BOOTP2: DHCPDefault: 2Range: 0 to 2F7-14(3F2) Duplex Mode SelectionSelects duplex mode setting.0: Half duplex forced1: Auto-negotiate duplex mode and communication speed2: Full duplex forcedDefault: <6>Range: 0 to 2F7-15(3F3)<7>Communication Speed SelectionSets the communication speed.0: 10 Mbps (Available only with drive software version PRG: 1012 to1015)1: 10 Mbps100: 100 MbpsDefault: <8>Range: <8>F7-16(3F4) Communication Loss Time-outSets the time-out value for communication loss detection in tenths of asecond. A value of 0 disables the connection time-out.Example: An entered value of 100 represents 10.0 seconds.Default: 0Min.: 0Max.: 300H5-11(43C)Communications ENTER FunctionSelectionSelect the function for the ENTER command that saves parameter data tothe drive.0: Parameter changes are activated when ENTER command is written1: Parameter changes are activated immediately without use of ENTERcommandDefault: 1Range: 0, 1<1> To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control the drive frequency referencevia the master device, set b1-01 to 3.<2> If F6-01 is set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as installing an emergency stopswitch.<3> Cycle power for setting changes to take effect.<4> If F7-13 is set to 0, then all IP Addresses (F7-01 to F7-04) must be unique.<5> Set F7-01 to F7-12 when F7-13 is set to 0.<6> Default setting differs by drive software version.1012 to 1015: 0≥1016: 1<7> Set F7-15 when F7-14 is set to 0 or 2.<8> The setting values differ by drive software version.1012 to 1015Default: 0Range: 0, 10, 100≥1016Default: 10Range: 10, 100No.(Addr. H) Name Description Values