6.3 Deployment of RS485 interface for PtPPer default, the RS485 interface is deactivated. Via hardware configuration the RS485interfaces may be switched to PtP operation (point to point) via the parameter FunctionRS485 of the Properties.Since the VIPA specific CPU parameters may be set, the installation of theSPEEDBUS.GSD from VIPA in the hardware catalog is necessary. The CPU may be con-figured in a PROFIBUS master system and the appropriate parameters may be set afterinstallation.The GSD (Geräte-Stamm-Datei) is online available in the following language versions.Further language versions are available on inquires:Name LanguageSPEEDBUS.GSD German (default)SPEEDBUS.GSG GermanSPEEDBUS.GSE EnglishThe GSD files may be found at www.vipa.com at the service area.The integration of the SPEEDBUS.GSD takes place with the following proceeding:1. Go to the service area of www.vipa.com.2. Load from the download area at ‘Config files è PROFIBUS’ the according file foryour System 300S.3. Extract the file to your work directory.4. Start the hardware configurator from Siemens.5. Close every project.6. Select ‘Options è Install new GSD-file’.7. Navigate to the directory VIPA_System_300S and select SPEEDBUS.GSD an.ð The SPEED7 CPUs and modules of the System 300S from VIPA may now befound in the hardware catalog at PROFIBUS-DP / Additional field devices / I/O /VIPA_SPEEDBUS.Activate RS485 to PtPoperationRequirementsInstallation of theSPEEDBUS.GSDVIPA System 300S+Deployment PtP communicationDeployment of RS485 interface for PtPHB140 | CPU | 317-2AJ23 | en | 17-2580