7.4 Deployment as PROFIBUS DP masterThe hardware configuration described before was established.1. Open the properties dialog of the DP interface of the CPU by means of a double-click at ‘MPI/DP’ .2. Set Interface type to "PROFIBUS"3. Connect to PROFIBUS and preset an address (preferably 2) and confirm with [OK].4. Switch at Operating mode to "DP master" and confirm the dialog with [OK]. APROFIBUS DP master system is inserted.ð A PROFIBUS DP master system is inserted:Now the project engineering of your PROFIBUS DP master is finished. Please link upnow your DP slaves with periphery to your DP master.1. For the project engineering of PROFIBUS DP slaves you search the concerningPROFIBUS DP slave in the hardware catalog and drag&drop it in the subnet of yourmaster.2. Assign a valid PROFIBUS address to the DP slave.3. Link up the modules of your DP slave system in the plugged sequence and add theaddresses that should be used by the modules.4. If needed, parameterize the modules.5. Save, compile and transfer your project.PreconditionProceedingVIPA System 300S+Deployment PROFIBUS communicationDeployment as PROFIBUS DP masterHB140 | CPU | 317-2AJ23 | en | 17-2596