Drive ModelFuse TypeManufacturer: BussmannModel Fuse Ampere Rating (A)5A0052 <1> FWP-175A 1755A0062 <1> FWP-250A 2505A0077 <1> FWP-250A 2505A0099 <1> FWP-250A 2505A0125 <1> FWP-350A 3505A0145 <1> FWP-350A 3505A0192 <1> FWP-600A 6005A0242 <1> FWP-600A 600<1> 600 V class drives are not compliant with European Standards.n GroundingThe drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of groundedsystems, contact your Yaskawa representative for instructions.n Guarding Against Harmful MaterialsWhen installing IP00/Open Type enclosure drives, use an enclosure that prevents foreign material from entering the drivefrom above or below.u EMC Guidelines ComplianceThis drive is tested according to European standards IEC/EN 61800-3: 2004.n EMC Filter InstallationThe following conditions must be met to ensure continued compliance with guidelines.Installation MethodVerify the following installation conditions to ensure that other devices and machinery used in combination with this drivealso comply with EMC guidelines.1. Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.2. Place the drive and EMC noise filter in the same enclosure.3. Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.4. Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.ABDECMU/T1V/T2W/T3UVWA – DriveB – 10 m max cable length betweendrive and motorC – MotorD – Metal conduitE – Ground wire should be as short aspossible.Figure i.34 Installation Method5. Make sure the protective earthing conductor complies with technical standards and local safety regulations.i.9 Standards Compliance100 YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide