5120410-XIM-B-021622 Johnson Controls Unitary ProductsTable 14: PHYSICAL DATAComponent11. R-407C units may require a super heat and sub-cooling check at the job site to ensure proper charge and operation.Models090 120 150EVAPORATORBLOWERBlower, CentrifugalDia. X Wd. in.(Dia. X Wd. mm.)12 X 12(305 X 305)15 X 15(381 X 381)15 X 15(381 X 381)Motor, Standard - HP (kW) 2 (1.5) 2 (1.5) 4 (3)Motor, Optional - HP (kW) 2 (1.5) 4 (3) N/AEVAPORATORCOILRows 2 3 4Fins Per 2.54 cm (1 in.) 15 15 15Height - in. (mm.) 32 (810) 40 (1020) 40 (1020)Face Area ft.2 (m2 ) 10.6 (0.98) 13.2 (1.23) 13.2 (1.23)CONDENSERFANS (2 perUnit)Propeller Dia. mm (in.) ea. 24 (610) 24 (610) 24 (610)Motor - Hp (kW) ea. 3/4 (0.56) 3/4 (0.56) 3/4 (0.56)Airflow - CFM (m3 /s) ea. 3700 (1.75) 3700 (1.75) 3700 (1.75)CONDENSERCOILS (2 perUnit)Rows (each) 1 1 2Fins Per Inch (2.54 mm) 20 20 20Height - in. (mm.) 28 (711) 44 (1120) 44 (1120)Face Area ft.2 (m2 ) 9.2 (.86) 14.5 (1.35) 14.5 (1.35)RefrigerantChargeSystem 1 - lbs. (kg.) 4.75 (2.15) 6.0 (2.72) 11.0 (4.99)System 2 - lbs. (kg.) 4.0 (1.81) 5.75 (2.61) 10.0 (4.54)COMPRESSORS Quantity 2 2 2Type Recip Recip ScrollAIRFILTERSSizeWd. x Ht. x Thickness in.(Wd. x Ht. x Thickness mm.)25x 16 x 2(635 x 406 x 51)25x 20 x 2(635 x 508 x 51)25x 20 x 2(635 x 508 x 51)