FORM 100.50-EG5 (108)35JOHNSON CONTROLSCURB LAYOUT DRAWINGLD08297FIG. 6 – GENERAL ARRANGEMENT DRAWINGNOTES:1. Unit must be installed square and level.2. Curb configuration for “bottom” return and “bottom” supply.3, These drawings are not intended as construction documents for the field-fabricated roof curbs. YORK will not be responsible for the unitfit-up, leak integrity, or sound level for installation using field-fabricated roof curbs.4. The YPAL unit does not have a base pan under the condensing section of the unit. Field-fabricated roof curbs must have a cap on the topof the condensing section of the curb to prevent moisture from entering the space. The cap design must be sloped away from the supply-duct opening to the end of the unit for the drainage of the moisture off of the top of the cap.229.5666.08333.6941.1971.8366.1921.0035.1014.0084.501.75TYPSUPPLYRETURN