036-21121-002 Rev. B (0103)Unitary Products Group 17Multipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above thelisted temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. H3RA060S06INDOOR COIL MODEL NO. G1FA060S21,24CONDENSERENTERING AIRTEMPERATUREID CFM 2050 1800 1550ID DB (°F) 85 80 70 85 80 70 85 80 70ID WB (°F) 72 67 57 72 67 57 72 67 5775T.C. 64.7 61.9 58.2 64.1 61.2 57.2 63.6 60.5 56.2S.C. 46.3 44.9 42.9 43.3 42.1 40.3 40.3 39.3 37.7K.W 5.18 5.13 5.03 5.08 5.02 4.92 4.97 4.91 4.8185T.C. 62.8 59.6 55.4 62.3 58.6 54.3 61.8 57.6 53.3S.C. 45.9 44.3 41.9 42.8 41.2 39.2 39.7 38.2 36.5K.W 4.94 4.86 4.77 5.58 5.50 5.40 5.48 5.40 5.2895T.C. 60.9 57.3 52.7 60.4 56.0 51.5 59.9 54.7 50.3S.C. 45.7 43.5 40.8 42.4 40.2 38.0 39.2 37.0 35.2K.W 6.19 6.10 6.00 6.09 5.99 5.87 5.98 5.88 5.74105T.C. 57.2 53.4 48.4 56.6 52.3 47.4 56.0 51.1 46.4S.C. 44.6 42.1 39.3 41.3 39.0 36.6 38.0 35.9 33.8K.W 6.82 6.70 6.56 6.71 6.59 6.44 6.60 6.47 6.31115T.C. 53.5 49.5 44.1 52.8 48.5 43.3 52.1 47.5 42.4S.C. 43.6 40.5 37.7 40.2 37.6 35.1 36.8 34.7 32.4K.W 7.47 7.32 7.14 7.35 7.19 7.01 7.22 7.06 6.88125T.C. 49.8 45.6 39.9 49.0 44.8 39.2 48.2 43.9 38.5S.C. 42.5 39.0 36.1 39.0 36.3 33.6 35.6 33.6 31.0K.W 8.12 7.94 7.72 7.99 7.79 7.58 7.84 7.65 7.45NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.Air Handler Coil T.C. S.C. KWN1AHD2006 G2FD060(S,H)24 1.00 1.00 1.00F2FP060 1.00 1.02 1.02G1HD060 0.99 1.00 1.01G1NA048S21D 0.91 0.87 0.96G1NA060S24T 0.98 0.99 0.99G1UA060S21,24 1.00 1.00 1.00G2FD060(S,H)24 1.00 1.00 1.00G2FD061H24 1.02 1.02 1.02