036-21121-002 Rev. B (0103)18 Unitary Products GroupMultipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above thelisted temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. H1RA060S(25,46)INDOOR COIL MODEL NO. G2FD060S24ACONDENSERENTERING AIRTEMPERATUREID CFM 1450 1700 1950ID DB (°F) 85 80 70 85 80 70 85 80 70ID WB (°F) 72 67 57 72 67 57 72 67 5775T.C. 61.2 58.5 56.3 61.8 59.1 56.9 62.3 59.6 57.5S.C. 37.6 37.4 37.1 40.1 39.9 39.5 42.5 42.3 41.8K.W 4.66 4.57 4.51 4.67 4.58 4.53 4.68 4.58 4.5585T.C. 60.6 58.0 55.0 61.2 58.6 55.8 61.9 59.3 56.7S.C. 37.6 37.3 36.5 40.2 39.9 39.1 42.8 42.5 41.7K.W 5.26 5.13 5.08 5.27 5.14 5.10 5.28 5.15 5.1195T.C. 60.0 57.4 53.7 60.7 58.5 54.8 61.4 59.0 55.8S.C. 37.5 37.1 35.9 40.3 39.8 38.8 43.1 42.6 41.6K.W 5.86 5.70 5.65 5.87 5.71 5.67 5.88 5.72 5.68105T.C. 58.1 54.6 50.0 58.9 55.7 51.3 59.7 56.8 52.7S.C. 36.9 36.0 34.4 39.8 39.0 37.3 42.7 41.9 40.2K.W 6.54 6.39 6.29 6.56 6.42 6.30 6.57 6.45 6.32115T.C. 56.2 51.8 46.3 57.1 53.2 47.9 57.9 54.5 49.5S.C. 36.2 34.9 32.9 39.3 38.1 35.9 42.3 41.2 38.8K.W 7.23 7.07 6.92 7.25 7.12 6.94 7.26 7.17 6.97125T.C. 54.3 49.0 42.6 55.2 50.6 44.5 56.2 52.3 46.4S.C. 35.6 33.8 31.4 38.7 37.2 34.4 41.9 40.5 37.4K.W 7.92 7.76 7.55 7.94 7.83 7.58 7.96 7.90 7.62Air Handler Coil T.C. S.C. KWN1AHD2046 G2FD060(S,H)24 1.00 1.00 1.00F2FP060 1.00 1.00 1.05G1FA060S21,24 1.00 1.00 1.00G1NA060S24T 0.98 0.98 1.01G1UA060S21,24 1.00 1.00 1.00