SM-16005-rev.2 5-17EXTERNAL INPUT/OUTPUT AND FUNCTION SETTINGNo. Items Optional Function IndividualSettingSettingCondition Contents1 b1Cancellation of HeatingTemperature Compensationdue to Uneven Heat Load○0001020304Standard (Set Temp. +7oF (+4oC))Removal (Set Temp.)Set Temp. +3oF (+2oC) (*1)Set Temp. +5oF (+3oC)Set Temp. +2oF (+1oC)2 b2 Circulator Function duringHeating Thermo-OFF ○ 0001Not AvailableAvailable3 b3 Not Prepared - - Not Used (Use as 00 conditions)4 b4 Change of Filter Cleaning Time -0001020304Standard 1,200 hrs (Factory-Setting)100 hrs1,200 hrs2,500 hrsNo Indication5 b5 Fixing of Operation Mode × 0001StandardFixed6 b6 Fixing of Setting Temperature × 0001StandardFixed7 b7 Fixing of Operation asExclusive Cooling Unit × 0001StandardFixed8 b8 Automatic COOL/HEAT Operation × 0001Not AvailableAvailable9 b9 Fixing of Fan Speed × 0001StandardFixed10 bA Not Prepared - - Not Used11 bb Cooling Temperature Compensationdue to Uneven Heat Load × 000102Standard (No Compensation)Set Temp. –2oF (–1oC)Set Temp. –3oF (–2oC)12 bC Not Prepared - - Not Used (Use as 00 conditions)13 bd Not Prepared - - Not Used (Use as 00 conditions)14 bE Not Prepared - - Not Used (Use as 00 conditions)15 C1 Not Prepared - - Not Used (Use as 00 conditions)16 C2 Not Prepared - - Not Used17 C3 Not Prepared - - Not Used18 C4 Not Prepared - - Not Used19 C5 EconoFresh Pressure Mode (*8) ○ 000102Not Available (Factory-Setting)EconoFresh Pressure ModeNot Available20 C6 Hi Speed during Heating Thermo-OFF ○ 0001Not AvailableAvailable21 C7Canceling of Enforced 3 MinutesMinimum Operation Time ofCompressor○ 0001StandardCancellation22 C8 Thermistor of Wired Controller (*6) ○000102Not AvailableControl by Thermistor of Wired ControllerControl by Average Value of Indoor Air InletThermistor and Thermistor of Wired Controller23 C9 Not Prepared - - Not Used24 CA Not Prepared - - Not Used25 Cb Selection of Forced Stoppage Logic × 0001Forced Stoppage Input: A ContactForced Stoppage Input: B Contact26 CC Not Prepared - - Not Used (Use as 00 conditions)● for Ducted (Medium Static) with EconoFresh Kit5.4.2.1 Function Selection Item5.4.2 Function Setting