SM-16005-rev.2 5-41EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING5.5.4 Comfort FunctionFollowing functions are not available depending on connected outdoor unit.(1) Quick FunctionDo not use the Quick Function when using the Ducted (EconoFresh). When it is used, the thermalload of heat source in the room may significantly increase depending on the outdoor temperatureconditions. Configure according to the outdoor temperature condition.(2) Power Up SettingIf the cooling/heating capacity seems insufficient during the normal operation, set this function.By setting this function, the target frequency and upper limit of the compressor are set higher asfollows.Setting ConditionPower Up ModeCompressor Frequency for Cooling Operation Compressor Frequency for Heating OperationUpper Limit Target Frequency Upper Limit Target Frequency0 (Default Setting) - - - -1 Default Setting +20% Default Setting +20% - -2 - - Default Setting +20% Default Setting +20%3 Default Setting +20% Default Setting +20% Default Setting +20% Default Setting +20%NOTE:The upper limit and target frequency of the compressor are same as Function Setting “Hc” or “Hh”.