035-17311-002-A-080312 Unitary Products GroupUnits may be moved or lifted with a forklift. Slotted openingsin the base rails are provided for this purpose.LENGTH OF FORKS MUST BE A MINIMUM OF 60INCHES.CLEARANCESAll units require particular clearances for proper operationand service. Installer must make provisions for adequateventilation air in accordance with applicable provisions of thelocal building codes. Refer to Table 6 for clearances requiredfor combustible construction, servicing, and proper unit oper-ation.Before lifting, make sure the unit weight is distrib-uted equally on the rigging cables so it will lift evenly.All panels must be secured in place when the unit islifted.The condenser coils should be protected from rig-ging cable damage with plywood or other suitablematerial.FIGURE 5 - UNIT 4 POINT LOADTABLE 3: UNIT WEIGHTSModel Shipping Weight* (lb.)*. Weights include largest gas heat option.Operating Weight † (lb.)†. 54kW heater.DM090 1056 1051DM120 1121 1116DM150 1200 1195Econ. 85 84w/ PE 150 148Elec. Heat 2 49 49DACBLETRONTTABLE 4: 6 POINT LOAD WEIGHTModel Location (lbs.) **. Weights include largest gas heat option.A B C D E FDM090 158 142 128 187 207 230DM120 168 151 136 198 219 244DM150 180 161 145 212 235 262TABLE 5: 4 POINT LOAD WEIGHTModel Location (lbs.) **. Weights include largest gas heat option.A B C DDM090 230 197 287 336DM120 245 209 305 357DM150 262 224 327 382FIGURE 6 - UNIT 6 POINT LOADFIGURE 7 - UNIT CENTER OF GRAVITYDACBELETRONTFRONTLEFT47 1/2" 25 1/2"