290699-YIM-B-0607Unitary Products Group 35TABLE 22: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATIONRPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 17202400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 16402300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 15352200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 14402100 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 13402000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 12251900 - - - - 894 885 940 940 980 980 1014 1020 1047 10951800 - - - - 855 815 903 860 950 905 988 940 1022 9701700 - - - - - - 884 815 925 850 964 880 1001 9101600 - - - - - - 864 770 908 805 948 835 987 8701500 - - - - - - - - 882 740 926 780 965 830RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS2500 - - - - - - - - - - - - - -2400 1193 1665 - - - - - - - - - - - -2300 1170 1580 1202 1620 - - - - - - - - - -2200 1148 1480 1180 1530 - - - - - - - - - -2100 1121 1385 1155 1425 1190 1475 - - - - - - - -2000 1100 1285 1133 1340 1169 1385 1205 1445 - - - - - -1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 - - - -1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 - - - -1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 - -1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 11501500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 111051, 2AVAILABLE EXTERNAL STATIC PRESSURE-IWG 30.90 1.00 1.10 1.20 1.30 1.40 1.50UNITTONNAGEAIR FLOWCFM51, 2UNITTONNAGEAIR FLOWCFM0.60 0.70 0.80AVAILABLE EXTERNAL STATIC PRESSURE-IWG 30.20 0.30 0.40 0.501. 230/460/575 Volts2. For 208 Volts multiply values by 0.95.3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table forresistance values on applications other than gas / electric units with side duct airflows.