556454-YTG-B-041022 Johnson Controls Unitary ProductsMultipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listedtemperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.Continued on next page.COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. TCHD30S41S3INDOOR COIL MODEL NO. FC/MC/PC35CONDENSINGENTERING AIRTEMPERATUREIDCFM 800 1000 1200ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 7265T.C. 27.3 28.7 28.9 30.5 31.8 28.8 29.9 29.8 31.6 33.4 30.3 31.0 30.7 32.8 35.0S.C. 26.6 24.5 20.7 20.5 15.9 28.2 27.4 23.2 22.6 17.2 29.7 30.4 25.7 24.7 18.5KW 1.61 1.64 1.61 1.64 1.63 1.63 1.63 1.61 1.64 1.64 1.65 1.62 1.61 1.64 1.6575T.C. 26.2 27.0 27.1 29.4 31.2 27.8 28.3 28.3 30.4 32.2 29.5 29.5 29.5 31.5 33.2S.C. 25.6 23.9 19.9 19.8 15.4 27.2 26.4 22.3 22.0 16.8 28.8 28.9 24.6 24.1 18.1KW 1.88 1.88 1.89 1.88 1.86 1.87 1.87 1.88 1.87 1.86 1.87 1.87 1.88 1.87 1.8685T.C. 25.1 25.3 25.2 28.3 30.6 26.8 26.7 26.7 29.2 31.0 28.6 28.0 28.3 30.1 31.4S.C. 24.5 23.2 19.1 19.2 15.0 26.2 25.3 21.3 21.3 16.3 28.0 27.4 23.6 23.5 17.7KW 2.15 2.12 2.18 2.11 2.09 2.12 2.12 2.16 2.10 2.09 2.09 2.12 2.14 2.10 2.0895T.C. 23.9 23.7 23.3 27.2 30.0 25.8 25.1 25.2 28.0 29.8 27.8 26.5 27.1 28.8 29.6S.C. 23.5 22.6 18.2 18.5 14.5 25.3 24.3 20.4 20.7 15.9 27.1 25.9 22.5 22.9 17.3KW 2.41 2.36 2.46 2.34 2.32 2.37 2.36 2.43 2.33 2.31 2.32 2.36 2.41 2.32 2.30105T.C. 22.4 22.6 22.2 25.0 27.8 24.3 24.1 23.8 26.1 27.8 26.2 25.6 25.3 27.3 27.9S.C. 21.9 21.5 17.6 17.8 13.9 23.7 23.1 19.7 20.0 15.3 25.5 24.8 21.7 22.2 16.7KW 2.93 2.96 3.05 2.84 2.70 2.85 2.88 3.01 2.80 2.69 2.76 2.80 2.97 2.76 2.67115T.C. 20.9 21.5 21.2 22.9 25.6 22.8 23.1 22.4 24.4 26.0 24.7 24.7 23.5 25.8 26.3S.C. 20.5 20.4 17.0 17.1 13.4 22.2 22.0 19.0 19.3 14.7 24.0 23.6 20.9 21.5 16.1KW 3.44 3.54 3.61 3.32 3.07 3.31 3.38 3.56 3.25 3.05 3.19 3.22 3.51 3.18 3.03125T.C. 19.5 20.4 20.1 20.7 23.4 21.3 22.1 20.9 22.6 24.1 23.2 23.9 21.8 24.4 24.7S.C. 19.0 19.3 16.4 16.4 12.8 20.7 20.9 18.3 18.6 14.2 22.4 22.5 20.1 20.8 15.5KW 3.94 4.13 4.18 3.81 3.44 3.78 3.88 4.12 3.70 3.42 3.62 3.63 4.06 3.60 3.39NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.Air Handlers Coils T.C. S.C. KW– FC/MC/PC30 0.99 0.98 1.00– FC/MC/PC32 1.00 1.00 1.00– FC/MC/PC36 1.00 0.99 1.00– FC/MC/PC37 1.01 1.02 1.00– FC/MC/PC43 1.01 1.02 1.00– HC30 0.99 0.98 1.00– HC36 1.00 1.00 1.00– HC42 1.01 1.02 1.00– HD36 0.99 0.96 1.00– UC30 0.99 0.98 0.99– UC48 0.96 0.96 1.00AHP36 – 1.01 1.02 1.00AHX30 – 1.01 1.03 0.97AHX36 – 1.04 1.04 0.94AHX42 – 1.05 1.06 0.92AHX48 – 1.06 1.11 0.93AV*36 – 1.03 1.03 0.93F*FP030 – 0.99 0.96 1.00F*FP036 – 0.99 0.99 0.99F*FP040 – 0.99 0.98 0.99F6FP030 – 1.01 1.01 1.01F6FP036 – 1.01 1.00 0.95F6FP042 – 1.06 1.08 0.94F6FP048 – 1.00 1.02 0.96MV12B FC/MC30B 1.01 1.00 0.93MV12B FC/MC35B 1.02 1.02 0.93MV16C FC/MC35C 1.02 1.02 0.93MV12B FC/MC36B 1.02 1.01 0.93MV16C FC/MC36C 1.02 1.01 0.93MV12B FC/MC43B 1.04 1.04 0.93MV16C FC/MC43C 1.04 1.04 0.92MV16C FC/MC48C 1.05 1.05 0.92Air Handlers Coils T.C. S.C. KW