556454-YTG-B-04106 Johnson Controls Unitary Products— = Not applicable.13 SEER AC WITH AHP / SHP / AHX / F*FPTCHD18S41S3AHX18 17 – 630 18.2 13.1 14.25 11.75AHX24 17 – 590 18.3 13.0 14.25 11.75AHX30 17 – 610 18.6 13.3 14.50 12.00F6FP018 17 – 600 17.9 12.6 13.50 11.25F6FP024 17 – 600 18.5 13.1 14.00 11.50F6FP030 17 – 620 18.5 13.2 14.00 11.50TCHD24S41S3AHP24 17 – 850 23.0 16.8 13.15 11.05AHX18 17 – 835 23.2 17.2 14.00 11.50AHX24 17 – 800 23.6 17.3 14.00 12.75AHX30 17 – 820 23.8 17.8 14.50 12.75AHX36 21 – 815 24.2 18.1 15.00 12.25F*FP030 17 – 800 23.0 16.7 13.10 11.00F6FP024 17 – 840 23.4 17.4 14.00 11.50F6FP030 17 – 850 23.4 17.4 13.75 11.25F6FP036 21 – 855 23.8 17.9 14.25 11.75TCHD30S41S3AHP36 21 – 1000 28.4 21.2 13.75 12.20AHX30 17 – 1025 28.4 21.3 14.50 12.50AHX36 21 – 1005 29.0 21.7 15.25 13.25AHX42 21 – 990 29.4 22.1 15.50 13.75AHX48 24 – 1090 29.8 23.0 15.50 13.75F*FP030 17 – 1000 27.6 20.0 13.20 11.85F*FP036 21 – 1000 27.8 20.6 13.40 12.00F*FP040 21 – 1000 27.8 20.4 13.40 12.00F6FP030 17 – 1035 28.2 20.9 13.75 12.00F6FP036 21 – 980 28.2 20.7 14.50 12.75F6FP042 21 – 1065 29.6 22.4 15.25 13.50F6FP048 24 – 1055 28.0 21.0 14.50 12.50TCHD36S41S3AHP36 21 – 1200 34.2 25.0 14.00 12.15AHX36 21 – 1225 34.4 25.7 14.75 12.50AHX42 21 – 1190 35.0 25.9 15.25 12.75AHX48 24 – 1255 35.2 26.3 15.25 12.75AHX60 24 – 1300 35.6 26.8 15.00 12.75F*FP036 21 – 1200 33.0 23.8 13.00 11.35F*FP040 21 – 1200 33.0 24.0 13.00 11.40F*FP042 21 – 1200 33.0 24.0 13.00 11.40F5FP048 24 – 1250 35.0 25.8 15.20 13.00F6FP036 21 – 1210 33.4 24.3 13.75 11.75F6FP042 21 – 1290 35.2 26.4 14.75 12.50F6FP048 24 – 1125 32.2 23.3 14.00 11.75F6FP060 24 – 1240 35.2 26.3 15.00 12.75TCHD48S41S3AHP/SHP60 24 – 1600 45.5 33.2 13.40 11.50AHX48 24 – 1660 47.0 34.6 13.75 11.75AHX60 24 – 1680 47.5 34.8 13.50 11.75F5FP048 24 – 1700 47.5 35.0 13.75 12.00F5FP060 24 – 1700 46.0 33.4 13.35 11.55F6FP048 24 – 1625 45.0 33.2 13.00 11.00F6FP060 24 – 1710 48.0 35.0 13.50 11.50TCHD60S41S3 AHX60 24 – 1905 57.5 40.2 13.00 11.00F6FP060 24 – 1710 56.5 38.7 13.00 11.00Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.Cooling MBH based on 8°F entering air temperature, 50% RH, and rated air flow.EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric powerinput in watt-hours during the same period.1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.COOLING CAPACITY - With Air Handler Coils (Continued)UNITMODELAIR HANDLER COILMODEL1COOLINGMODEL W RATEDCFMNET MBH SEER EERTOTAL SENS.