19Coil Data - Air HandlerModel Nomenclature - Air HandlerCompatibility Table - Air HandlerAFFINITY INDOOR SPLIT SERIES INSTALLATION MANUALAffi nity Split Model Matching Air Handler Coil Surface Area (ft2) FPI Rows Tube Diameter022 - 038 YAH036 5.83 12 2 3/8 in.042 - 072 YAH060 5.83 12 3 3/8 in.YAH 036 * 00 0 1 R1-3 4-6 7 8-9 10 11 12ModelYAH – Affinity Series Air HandlerUnit CapacityRefrigeration (DX) Models with Nominal CFM022 MBTUH 800026 MBTUH 925030 MBTUH 980036 MBTUH 1225042 MBTUH 1425048 MBTUH 1625060 MBTUH 1760Hydronic Models with Nominal CFM026 MBTUH 925036 MBTUH 1225048 MBTUH 1625060 MBTUH 1760Vintage* = Factory Use OnlyAir CoilR – RefrigerantH - HydronicMotor1 – ECM 208-230/60/1Disconnect0 – No Breaker Installed(only on 5kW & 10kW Heaters)1 – Breaker Installed(only on 15kW & 20kW Heaters)Electric Heat00 – None05 – 5kW (022 – 036 only)10 – 10kW (030 – 060 only)15 – 15kW (042 – 060 only)20 – 20kW (060 only)Rev.: 16 August 2013DNOTE: To field convert the YAH042-060 to bottomflow air discharge, the NAHBC kit must be ordered.Air Handler Sizing SelectionAir handlers should be designed for R-410A refrigerant and should be matched with the outdoor split compressor section according to thetable below.Air Handler Indoor Split Model(Single)Indoor Split Model(Dual Capacity)Outdoor Split Model(Dual Capacity) Airflow (CFM) Electric Heat (kW)YAH022A***1R YAZS022 - 800 5YAH026A***1R - YAZT026 YAST026 925 5YAH030A***1R YAZS030 - - 980 5, 10YAH036A***1R YAZS036 - - 1225 5, 10YAH036A***1R - YAZT038 YAST038 1225 5, 10YAH042A***1R YAZS042 - - 1425 10, 15YAH048A***1R YAZS048 - - 1625 10, 15YAH048A***1R - YAZT049 YAST049 1625 10, 15YAH060A***1R YAZS060 - - 1760 10, 15, 20YAH060A***1R - YAZT064 YAST064 1760 10, 15, 20YAH060A***1R YAZS070 - - 1760 10, 15, 20YAH060A***1R - YAZT072 YAST072 1760 10, 15, 20