37Heat of Extraction/Rejection Data - Dual Capacity UnitsModel GPM Heat of Extraction (kBtuh) Heat of Rejection (kBtuh)30°F 50°F 70°F 90°F 30°F 50°F 70°F 90°F 110°F026Part Load3.0 13.1 17.6 21.5 23.5 22.9 21.85.0 9.4 13.8 18.6 22.6 21.7 23.6 23.0 21.7 20.27.0 9.6 14.1 18.9 23.0 21.9 23.7 23.1 21.7 20.2Full Load4.0 17.8 23.4 28.5 31.0 31.2 30.06.0 13.4 18.8 24.7 29.9 29.9 31.1 31.3 29.9 28.18.0 13.6 19.3 25.1 30.5 30.1 31.2 31.3 29.9 28.1038Part Load4.0 17.9 23.3 28.1 32.5 31.8 30.06.0 12.8 18.7 24.5 29.8 29.8 32.7 32.0 30.1 28.28.0 13.9 19.7 25.2 29.8 30.3 33.1 32.4 30.4 28.5Full Load5.0 25.1 31..5 36.1 44.8 45.1 42.87.0 18.7 26.2 33.2 38.6 41.8 45.2 45.7 43.6 41.09.0 19.1 26.9 34.3 40.0 42.0 45.5 46.0 43.8 41.1049Part Load5.0 24.0 29.5 33.7 44.9 46.1 44.08.0 19.2 26.4 32.6 37.5 40.6 45.0 45.8 43.4 40.511.0 19.8 27.5 34.3 39.9 40.0 44.9 46.1 44.3 41.5Full Load6.0 33.3 40.6 46.1 60.2 60.2 56.49.0 26.0 34.7 42.8 49.1 56.0 60.2 60.8 57.4 52.912.0 26.5 35.7 44.2 50.9 56.1 60.4 61.1 57.6 53.2064Part Load6.0 31.0 39.2 46.1 56.3 55.4 52.110.0 21.6 31.4 40.9 49.7 52.4 56.2 55.5 52.4 49.414.0 22.6 32.6 41.7 49.8 52.2 56.2 55.6 52.6 49.7Full Load8.0 40.8 52.7 64.7 73.7 75.7 70.312.0 31.9 43.8 55.1 65.8 66.8 74.1 76.1 70.5 66.216.0 32.2 44.7 56.8 68.6 67.2 74.5 76.5 70.9 66.3072Part Load10.0 36.4 46.5 54.7 63.4 63.0 58.913.0 25.2 36.7 48.5 59.1 57.7 63.2 63.0 59.2 55.116.0 26.7 38.2 49.4 59.1 57.3 63.2 63.3 59.5 55.4Full Load12.0 48.3 62.7 69.0 81.8 83.0 77.815.0 37.2 51.6 65.4 70.9 73.6 82.1 83.3 78.0 71.918.0 37.6 52.7 67.5 73.5 74.1 82.6 83.8 78.4 72.2Note: operation not recommended in shaded areas. 1/14/2011AFFINITY INDOOR SPLIT SERIES INSTALLATION MANUAL