840569-YTG-B-1012Johnson Controls Unitary Products 15Multipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listedtemperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. YCJD18S41S1(H)(E)INDOOR COIL MODEL NO. FC/MC/PC18CONDENSINGENTERING AIRTEMPERATUREIDCFM 450 600 750ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 7265T.C. 16.3 18.4 18.3 20.1 20.7 17.5 19.0 18.7 20.2 20.9 18.7 19.6 19.1 20.3 21.1S.C. 16.3 14.5 12.7 12.6 9.7 17.5 17.1 14.2 13.6 10.3 18.7 17.2 15.7 14.6 10.9KW 1.16 1.16 1.16 1.15 1.14 1.21 1.21 1.21 1.20 1.20 1.26 1.26 1.27 1.26 1.2575T.C. 15.6 17.4 17.3 19.0 19.9 16.8 18.1 17.7 19.3 20.1 18.1 18.8 18.2 19.5 20.3S.C. 15.6 14.3 12.2 12.2 9.3 16.8 16.3 13.8 13.4 10.1 18.1 18.4 15.4 14.6 10.8KW 1.28 1.28 1.28 1.28 1.27 1.34 1.34 1.34 1.33 1.33 1.39 1.39 1.39 1.39 1.3985T.C. 14.8 16.4 16.2 18.0 19.2 16.1 17.2 16.7 18.4 19.3 17.4 18.0 17.3 18.8 19.5S.C. 14.8 14.0 11.8 11.7 9.0 16.1 15.6 13.5 13.2 9.8 17.4 17.2 15.1 14.6 10.6KW 1.40 1.41 1.40 1.41 1.41 1.46 1.46 1.46 1.46 1.47 1.52 1.52 1.52 1.52 1.5295T.C. 14.0 15.4 15.1 17.0 18.4 15.4 16.3 15.8 17.5 18.6 16.7 17.2 16.4 18.0 18.7S.C. 14.0 13.8 11.3 11.3 8.6 15.4 14.8 13.1 13.0 9.6 16.7 15.9 14.9 14.6 10.5KW 1.53 1.53 1.53 1.53 1.54 1.59 1.59 1.59 1.59 1.60 1.65 1.65 1.65 1.65 1.66105T.C. 13.0 14.2 13.7 15.6 17.1 14.3 15.1 14.3 16.1 17.3 15.5 16.1 15.0 16.6 17.4S.C. 13.0 13.1 10.7 10.8 8.3 14.3 14.0 12.4 12.5 9.3 15.5 14.9 14.0 14.3 10.3KW 1.69 1.69 1.69 1.70 1.71 1.75 1.75 1.75 1.76 1.77 1.82 1.82 1.81 1.82 1.83115T.C. 12.1 13.0 12.3 14.3 15.9 13.2 14.0 13.0 14.7 16.0 14.3 15.0 13.6 15.2 16.2S.C. 12.1 12.4 10.1 10.3 8.0 13.2 13.1 11.7 12.1 9.0 14.3 13.8 13.2 13.9 10.1KW 1.85 1.85 1.84 1.85 1.87 1.91 1.91 1.91 1.92 1.94 1.98 1.98 1.97 1.98 2.00125T.C. 11.1 11.9 10.9 12.9 14.7 12.1 12.9 11.6 13.4 14.8 13.1 13.9 12.3 13.8 14.9S.C. 11.1 11.8 9.5 9.8 7.6 12.1 12.3 10.9 11.7 8.7 13.1 12.8 12.3 13.5 9.8KW 2.00 2.00 1.99 2.01 2.04 2.08 2.07 2.06 2.08 2.10 2.15 2.14 2.13 2.15 2.16NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).Air Handlers Coils T.C. S.C. KW– FC/MC/PC18 1.00 1.00 1.00– UC18 1.00 1.00 1.00AHE18B – 1.02 1.07 0.92AHR18B – 1.02 1.07 1.02AHV18B – 1.01 1.04 0.90AHV24B – 1.02 1.05 0.90AHV30B – 1.03 1.12 0.91AHV36C – 1.04 1.12 0.90AV*24 – 1.03 1.05 0.94MV12B FC/MC18B 1.00 1.03 0.88MX12B FC/MC18B 1.02 1.05 0.90Furnaces Coils T.C. S.C. KWT*(8,L)V*A12 FC/MC/PC18A 1.00 0.98 0.88T*(8,L)V*A12 UC18A 1.00 0.98 0.92T*(8,L)V*B12 FC/MC/PC18B 1.00 0.98 0.92T*(8,L)V*B12 UC18B 1.00 0.97 0.92T*(8,L)X*A12 FC/MC/PC18A 1.01 1.00 0.89T*(8,L)X*A12 UC18A 1.01 1.04 0.93T*(8,L)X*B12 FC/MC/PC18B 1.03 1.04 0.91T*(8,L)X*B12 UC18B 1.03 1.04 0.94T*9V*A10 FC/MC/PC18A 1.03 1.03 0.91T*9(C,V)*B12 FC/MC/PC18B 1.00 0.99 0.88T*9(C,V)*B12 UC18B 1.00 0.98 0.88T*9X*A10 FC/MC/PC18A 1.01 1.00 0.93T*9X*B12 FC/MC/PC18B 1.03 1.04 0.91T*9X*B12 UC18B 1.03 1.04 0.94Y*(8,L)C*A12 FC/MC/PC18A 1.00 0.98 0.88Y*(8,L)C*A12 UC18A 1.00 0.98 0.92Y*(8,L)C*B12 FC/MC/PC18B 1.00 0.98 0.92Y*(8,L)C*B12 UC18B 1.00 0.97 0.92Y*9C*B12 FC/MC/PC18B 1.00 0.99 0.88Y*9C*B12 UC18B 1.00 0.98 0.88