840569-YTG-B-101220 Johnson Controls Unitary ProductsMultipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listedtemperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.Continued on next page.COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. YCJD36S41S1(H)(E)INDOOR COIL MODEL NO. FC/MC/PC37CONDENSINGENTERING AIRTEMPERATUREIDCFM 1000 1200 1400ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 7265T.C. 35.3 37.4 37.0 39.3 40.4 36.3 38.1 37.4 39.7 40.2 37.3 38.8 37.8 40.1 40.1S.C. 33.1 29.8 25.3 24.2 18.1 34.1 31.8 26.8 25.2 18.5 35.2 33.8 28.3 26.1 18.9KW 2.40 2.42 2.41 2.44 2.44 2.49 2.50 2.50 2.53 2.53 2.58 2.58 2.60 2.61 2.6375T.C. 33.8 35.6 35.1 37.7 39.3 34.9 36.4 35.6 38.1 39.3 36.1 37.2 36.1 38.5 39.3S.C. 31.7 29.4 24.8 23.9 17.9 32.9 31.4 26.5 25.1 18.5 34.1 33.3 28.2 26.3 19.1KW 2.61 2.63 2.62 2.66 2.67 2.71 2.72 2.71 2.75 2.77 2.80 2.80 2.80 2.83 2.8685T.C. 32.4 33.8 33.3 36.2 38.1 33.6 34.7 33.8 36.6 38.3 34.8 35.6 34.4 37.0 38.4S.C. 30.4 29.0 24.3 23.5 17.7 31.7 30.9 26.1 25.0 18.5 33.0 32.8 28.0 26.5 19.3KW 2.82 2.84 2.84 2.88 2.91 2.92 2.93 2.92 2.96 3.00 3.02 3.03 3.01 3.05 3.0995T.C. 31.0 32.0 31.5 34.6 37.0 32.3 33.0 32.1 35.0 37.3 33.6 34.0 32.7 35.4 37.6S.C. 29.0 28.6 23.7 23.1 17.5 30.5 30.5 25.8 24.9 18.5 31.9 32.3 27.9 26.6 19.5KW 3.04 3.05 3.05 3.09 3.14 3.14 3.15 3.13 3.18 3.23 3.24 3.25 3.22 3.27 3.32105T.C. 28.0 28.9 27.8 31.1 34.3 28.9 29.9 28.5 31.6 34.6 29.9 30.9 29.2 32.0 34.9S.C. 26.3 26.2 22.0 21.9 16.6 27.4 27.8 23.8 23.8 17.7 28.5 29.4 25.6 25.7 18.9KW 3.25 3.25 3.23 3.30 3.37 3.36 3.36 3.33 3.39 3.47 3.47 3.47 3.43 3.49 3.56115T.C. 25.0 25.9 24.3 27.8 31.7 25.7 26.9 25.1 28.2 32.0 26.4 27.9 25.9 28.7 32.3S.C. 23.7 23.9 20.3 20.8 15.8 24.4 25.2 21.8 22.8 17.0 25.2 26.6 23.4 24.7 18.3KW 3.45 3.46 3.42 3.50 3.60 3.57 3.57 3.52 3.60 3.70 3.68 3.69 3.63 3.70 3.79125T.C. 22.1 22.9 20.7 24.4 29.0 22.5 23.9 21.7 24.9 29.3 22.9 24.9 22.6 25.4 29.6S.C. 21.1 21.5 18.6 19.7 15.0 21.5 22.7 19.9 21.7 16.3 21.9 23.8 21.1 23.8 17.7KW 3.65 3.66 3.60 3.70 3.83 3.78 3.78 3.71 3.80 3.93 3.90 3.91 3.83 3.91 4.03NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).Air Handlers Coils T.C. S.C. KW– FC/MC/PC37 1.00 1.00 1.00– FC/MC/PC43 1.00 1.00 1.00– FC/MC/PC48 1.00 1.00 1.00– UC48 1.00 1.00 1.00AHE36C – 1.02 1.02 0.93AHE42D – 1.02 1.04 0.92AHR36B – 0.99 0.99 0.99AHR42C – 1.02 1.02 0.99AHV36C – 1.02 1.04 0.94AHV42D – 1.03 1.04 0.92AHV48D – 1.02 1.02 0.91AV*36 – 1.00 1.02 0.92MV12B FC/MC43B 1.01 1.02 0.95MV12D FC/MC48D 1.00 1.02 0.92MV16C FC/MC43C 1.03 1.02 0.94MV16C FC/MC48C 1.03 1.02 0.94MV20D FC/MC48D 1.03 1.03 0.94MX12B FC/MC43B 1.01 1.02 0.95MX12D FC/MC48D 1.03 1.03 0.92MX16C FC/MC43C 1.01 1.01 0.91MX16C FC/MC48C 1.03 1.03 0.91