571209-YTG-B-121122 Johnson Controls Unitary ProductsMultipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listedtemperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.COOLING PERFORMANCE DATACONDENSING UNIT MODEL NO. YHJD18S41S2INDOOR COIL MODEL NO. FC35CONDENSINGENTERING AIRTEMPERATUREIDCFM 450 600 750ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 7265T.C. 16.8 18.5 18.8 20.3 21.7 18.9 19.4 19.9 21.3 22.3 21.0 20.3 20.9 22.2 22.9S.C. 16.8 15.4 13.3 13.2 11.1 18.9 18.2 15.6 15.1 12.0 21.0 20.3 17.8 17.0 12.9KW 1.0 1.0 1.0 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.2 1.2 1.2 1.2 1.275T.C. 16.0 17.6 17.6 19.4 20.9 18.0 18.5 18.7 20.3 21.6 20.0 19.5 19.7 21.2 22.2S.C. 16.0 14.9 12.8 12.8 10.6 18.0 17.6 15.0 14.7 11.6 20.0 19.5 17.3 16.7 12.6KW 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.3 1.3 1.3 1.3 1.385T.C. 15.2 16.6 16.5 18.5 20.1 17.1 17.7 17.5 19.4 20.8 19.0 18.8 18.5 20.2 21.5S.C. 15.2 14.4 12.2 12.4 10.2 17.1 17.0 14.5 14.4 11.2 19.0 18.8 16.7 16.4 12.3KW 1.3 1.3 1.3 1.3 1.3 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.5 1.5 1.595T.C. 14.4 15.6 15.3 17.7 19.3 16.2 16.8 16.3 18.5 20.1 18.0 18.0 17.3 19.2 20.8S.C. 14.4 13.9 11.7 11.9 9.7 16.2 16.3 13.9 14.0 10.8 18.0 18.0 16.2 16.1 11.9KW 1.4 1.4 1.4 1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.6 1.6 1.6 1.6 1.6105T.C. 13.5 14.2 14.1 16.2 18.0 15.2 15.6 15.0 17.0 18.7 16.9 16.9 15.8 17.8 19.4S.C. 13.5 13.3 11.1 11.3 9.1 15.2 15.4 13.3 13.4 10.3 16.9 16.9 15.5 15.5 11.5KW 1.6 1.6 1.6 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.8 1.8 1.7 1.8 1.8115T.C. 12.5 12.8 12.8 14.8 16.7 14.2 14.3 13.6 15.6 17.4 15.9 15.9 14.4 16.3 18.0S.C. 12.5 12.6 10.5 10.7 8.6 14.2 14.3 12.7 12.8 9.8 15.9 15.9 14.4 14.9 11.0KW 1.7 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9 1.9 2.0125T.C. 11.5 11.4 11.6 13.4 15.5 13.2 13.1 12.2 14.1 16.0 14.8 14.8 12.9 14.9 16.6S.C. 11.5 11.4 9.9 10.0 8.0 13.2 13.1 12.1 12.2 9.3 14.8 14.8 12.9 14.4 10.6KW 1.9 1.9 1.9 1.9 2.0 2.0 2.0 2.0 2.0 2.0 2.1 2.1 2.1 2.1 2.1NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).Air Handlers Coils T.C. S.C. KW– FC/MC/PC18 0.99 0.99 1.00– FC/MC/PC24 1.01 1.01 1.00– HD24 1.03 1.02 1.00AHE18B – 0.97 0.99 1.01AHP18 – 1.00 1.00 1.00AHP24 – 1.00 1.00 1.00AHR18B – 0.97 1.01 1.10AHX18 – 1.03 1.02 1.00AV*24 – 1.03 1.02 1.00F4FP024 – 1.00 0.99 1.00F6FP018 – 1.03 1.02 1.00F6FP024 – 1.03 1.02 1.00MX12B FC/MC18B 0.97 0.98 0.85MX12B FC/MC24B 0.97 1.02 1.01MX12B FC/MC30B 0.97 1.02 1.01MV12B FC/MC18B 1.02 1.01 1.00MV12B FC/MC24B 1.04 1.04 1.00Furnaces Coils T.C. S.C. KWT*(8,L)X*A12 FC/MC/PC18A 1.04 1.06 0.94T*(8,L)X*B12 FC/MC/PC18B 1.04 1.06 0.94T*9X*B12 FC/MC/PC18B 1.04 1.06 0.94T*(8,L)X*A12 FC/MC/PC24A 1.06 1.08 0.92T*(8,L)X*B12 FC/MC/PC24B 1.06 1.08 0.92T*9X*B12 FC/MC/PC24B 1.06 1.08 0.92T*(8,L)X*A12 FC/MC/PC30A 1.06 1.08 0.92T*(8,L)X*B12 FC/MC/PC30B 1.06 1.08 0.92T*9X*B12 FC/MC/PC18A 1.06 1.08 0.92(Y*LC/T*8V/T*LV)*A12 FC/MC/PC18A 1.03 1.05 0.93(Y*LC/T*8V/T*LV)*B12 FC/MC/PC18B 1.02 1.01 0.92(Y*9C/T*9V)*B12 FC/MC/PC18B 1.03 1.04 0.92(Y*LC/T*8V/T*LV)*A12 FC/MC/PC24A 1.06 1.08 0.94(Y*LC/T*8V/T*LV)*B12 FC/MC/PC24B 1.04 1.04 0.92(Y*9C/T*9V)*B12 FC/MC/PC24B 1.06 1.08 0.93(Y*LC/T*8V/T*LV)*A12 FC/MC/PC30A 1.06 1.08 0.94(Y*LC/T*8V/T*LV)*B12 FC/MC/PC30B 1.04 1.04 0.92(Y*9C/T*9V)*B12 FC/MC/PC30B 1.06 1.08 0.93(Y*LC/T*8V/T*LV)*A12 HD24 1.06 1.08 0.94(Y*LC/T*8V/T*LV)*B12 HD24 1.05 1.04 0.92(Y*9C/T*9V)*B12 HD24 1.06 1.08 0.93(Y*LC/T*8V/T*LV)*A12 UC18A 1.04 1.05 0.93(Y*LC/T*8V/T*LV)*B12 UC18B 1.03 1.03 0.92(Y*9C/T*9V)*B12 UC18B 1.04 1.05 0.92(Y*LC/T*8V/T*LV)*A12 UC24A 1.06 1.09 0.94(Y*LC/T*8V/T*LV)*B12 UC24B 1.05 1.05 0.92(Y*9C/T*9V)*B12 UC24B 1.06 1.09 0.93(Y*LC/T*8V/T*LV)*A12 UC30A 1.06 1.09 0.94(Y*LC/T*8V/T*LV)*B12 UC30B 1.05 1.05 0.92(Y*9C/T*9V)*B12 UC30B 1.06 1.09 0.93Furnaces Coils T.C. S.C. KW