571209-YTG-B-1211Johnson Controls Unitary Products 25Multipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listedtemperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.Continued on next page.COOLING PERFORMANCE DATACONDENSING UNIT MODEL NO. YHJD36S41S4INDOOR COIL MODEL NO. AHP36CONDENSINGENTERING AIRTEMPERATUREIDCFM 1000 1200 1400ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 7265T.C. 35.0 39.8 39.9 42.7 45.2 37.7 40.6 41.0 43.5 45.7 40.5 41.5 42.0 44.4 46.1S.C. 34.9 32.4 27.9 27.1 22.7 37.7 35.4 29.9 28.6 23.2 40.4 38.5 31.8 30.2 23.8KW 2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.6 2.6 2.6 2.675T.C. 33.3 36.8 36.9 39.9 42.9 35.7 37.6 37.9 40.8 43.4 38.1 38.5 38.9 41.8 43.9S.C. 33.2 31.1 26.5 25.9 21.5 35.7 33.7 28.5 27.6 22.2 38.1 36.4 30.5 29.4 22.9KW 2.6 2.6 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.885T.C. 31.6 33.8 33.9 37.1 40.6 33.7 34.6 34.8 38.2 41.2 35.8 35.5 35.7 39.2 41.8S.C. 31.5 29.7 25.1 24.8 20.2 33.6 32.1 27.2 26.7 21.1 35.7 34.4 29.2 28.5 22.0KW 2.8 2.8 2.8 2.9 2.9 2.9 2.9 2.9 2.9 3.0 3.0 3.0 3.0 3.0 3.195T.C. 29.9 30.8 30.8 34.3 38.4 31.7 31.6 31.7 35.5 39.0 33.5 32.5 32.6 36.6 39.6S.C. 29.8 28.4 23.7 23.6 19.0 31.6 30.4 25.8 25.7 20.1 33.4 32.4 27.9 27.7 21.1KW 2.9 2.9 3.0 3.1 3.1 3.0 3.1 3.1 3.1 3.2 3.2 3.2 3.2 3.2 3.3105T.C. 26.3 26.7 27.4 31.4 35.3 28.6 28.5 28.1 32.4 35.9 30.9 30.4 28.8 33.3 36.5S.C. 26.3 25.5 22.3 22.4 17.8 28.6 27.9 24.3 24.5 18.9 30.9 30.4 26.3 26.5 20.0KW 3.1 3.1 3.1 3.2 3.3 3.2 3.2 3.2 3.3 3.4 3.3 3.3 3.3 3.4 3.5115T.C. 22.8 22.6 24.1 28.5 32.2 25.6 25.5 24.5 29.2 32.8 28.4 28.4 25.0 30.0 33.5S.C. 22.8 22.5 20.8 21.3 16.6 25.5 25.4 22.8 23.3 17.8 28.3 28.3 24.8 25.3 18.9KW 3.2 3.2 3.2 3.4 3.5 3.4 3.4 3.3 3.5 3.6 3.5 3.5 3.4 3.6 3.6125T.C. 19.3 18.4 20.7 25.6 29.1 22.5 22.4 20.9 26.1 29.8 25.8 26.4 21.2 26.7 30.4S.C. 19.2 18.4 19.3 20.1 15.4 22.5 22.4 20.9 22.1 16.6 25.8 26.3 21.2 24.0 17.8KW 3.4 3.4 3.3 3.5 3.7 3.6 3.5 3.5 3.6 3.7 3.7 3.7 3.6 3.8 3.8NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).Air Handlers Coils T.C. S.C. KW– FC/MC/PC37 1.00 1.01 1.04– FC/MC/PC43 1.00 1.00 1.04– FC/MC/PC48 1.00 1.00 1.04– HD48 1.00 0.99 1.04– UC48 1.00 1.01 1.04AHE36C – 0.98 0.99 0.94AHE42D – 0.98 0.99 0.94AHP42 – 1.00 1.02 1.04AHR36B – 0.98 1.00 1.02AHR42C – 0.98 0.99 1.02AHX36 – 1.00 1.01 0.95AHX42 – 1.00 1.01 0.95AV*36 – 1.00 1.01 0.95F5FP048 – 1.00 1.02 0.95F6FP042 – 1.00 1.04 0.95MX12B FC/MC43B 0.98 1.00 0.94MX16C FC/MC43C 0.98 0.98 0.94MX12D FC/MC48D 0.98 0.99 0.94MX16C FC/MC48C 0.98 0.99 0.94MV12B FC/MC43B 1.00 1.02 0.95MV12D FC/MC48D 1.00 1.00 0.95MV16C FC/MC43C 1.00 1.01 0.95MV16C FC/MC48C 1.00 1.00 0.95Air Handlers Coils T.C. S.C. KW