SECTION 2 - ALL UNITSFORM 145.05-SU3 (611)ISSUE DATE 6/01/2011JOHNSON CONTROLS7SECTION 2 - ALL UNITSON / OFF - MANUAL SWITCHTo turn the unit ON turn the ON/AUTO/OFF toggleswitch, located below the User Interface, from theOFF to ON position.Field WiringNone Required.ProgrammingPROGRAM KEY - Unit Data Subsection• CLOCK SCHEDULE = USER DISABLEDON / OFF - INTERNAL CLOCKTo turn the unit ON, turn the ON/AUTO/OFF toggleswitch, located below the User Interface, from the OFFto AUTO position. The unit will then be switched toON based on the OCCUPIED schedule programmedin the User Interface.Field WiringNone required.ProgrammingPROGRAM KEY - Unit Data Subsection• CLOCK SCHEDULE = USER ENABLEDON / OFF - COMMUNICATEDTo turn the unit ON turn the ON/AUTO/OFF toggleswitch, located below the User Interface, from theOFF to AUTO position. The unit will then be switchedto ON based on a communicated OCCUPIED input.Field WiringConnect the (+) wire of a shielded twisted pair to the(+) terminal of the TB1 connector.Connect the (-) wire of a shielded twisted pair to the (-)terminal of the TB1 connector.ProgrammingPROGRAM KEY - Unit Data Subsection.• CLOCK SCHEDULE = USER DISABLED