826081-XIM-C-021418 Johnson Controls Unitary ProductsZF036-076 Unit WeightsFigure 9: Unit 4 Point Load Weight Figure 10: Unit 6 Point Load WeightADBFrontCAFCB FrontDETable 5: ZF036-076 ImperialSize(Tons) Model Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) 6 Point Load Location (lbs.)Shipping Operating X Y A B C D A B C D E F036(3.0) ZF036 502 497 39.6 19.4 111 103 136 146 75 72 68 89 94 99048(4.0) ZF048 525 520 39.2 18.9 115 104 143 158 78 73 69 94 100 107060(5.0) ZF060 554 549 39.2 18.9 121 110 151 166 82 77 72 99 106 113076(6.3) ZF076 584 579 37.7 18.4 128 109 156 185 88 79 71 101 113 127X YLEFT FRONTTable 6: ZF036-076 MetricSize(Tons) Model Weight (kg.) Center of Gravity (mm) 4 point Load Location (kg.) 6 point Load Location (kg.)Shipping Operating X Y A B C D A B C D E F036(3.0) ZF036 228 225 1005.8 492.8 50.3 46.7 61.7 61.7 34.0 32.7 30.8 40.4 42.6 44.9048(4.0) ZF048 238 236 995.7 480.1 52.2 47.2 64.9 71.7 35.4 33.1 31.3 42.6 45.5 48.5060(5.0) ZF060 251 249 995.7 480.1 54.9 49.9 68.5 75.3 37.2 34.9 32.7 44.9 48.1 51.3076(6.3) ZF076 265 263 957.6 467.4 58.1 49.4 70.8 83.9 39.9 35.8 32.2 45.8 51.3 57.6Table 7: ZF036-076 Unit Accessory WeightsUnit Accessory Weight (lbs.)Shipping OperatingEconomizer 55 50Power Exhaust 55 50Electric Heat 1 28 28Gas Heat 2 70 701. Weight given is for the maximum heater size available(30KW).2. Weight given is for the maximum number of tube heatexchangers available (5 tube).