9.6.2.4 Limit ON / OFF, Function |3D|The value for “Limit” adjusted in the Controller Setup, is activated over a digital input.Contact at digital input e.g. “Digital In 1”.For “D1” Inverting“OFF”, limitation active at closed contact.ControllerD1 D110n = 0- 80 %10- - - - -n = 0- 100 %27.11.2008v_3d_limit_m.vsd1M9.6.2.5 Switch over Input signal “E1” / “E2”, Function |4D |Switch over between Input signal 1 (Analog In 1 terminal “E1”) and input signal 2 (Analog In 2 terminal“E2”).Contact at digital input e.g. “Digital In 1”= terminals “D1” - “D1”D1 D110n = 0- 100 %01Si 1Si 2E1GNDE2GNDSi 1Si 227.11.2008v_4d_umschaltung_e1_e2_m.vsdControllerMSi 1 Signal 1Si 2 Signal 2For mode speed controller ( 1.10 ... 1.10 ) Base setup for “E2 Analog In”: |1E| necessary.For modes controller (higher 3.10 ... 3.22 ) Base setup for “E2 Analog In”: |7E| necessary (as far asotherwise does not occupy).9.6.2.6 Set 1/2 or Setpoint 1/2, Function |5D|Switch over between “Set Intern1” and “Set Intern2” (for speed controller 1.10 ... 1.11 ).Contact at digital input e.g. “Digital In 1”.ControllerD1 D110n = 40 %1n = 80 %0- - - - -- - - - -27.11.2008v_5d_vorgabe_intern_1_2_m.vsd12 M• “D1 Inverting” = “OFF”: “Set Intern1” atopened contact / “Set Intern2” at closedcontact.• “D1 Inverting” = “ON”: “Set Intern1” atclosed contact / “Set Intern2” at openedcontact.FrequencyOperation with “Set Intern2” is signalized by the moon symbol for reduced operation.“Set extern1” under “settings” must be programmed to “OFF”.Operating Instructions Fcontrol – model series FKDM..-C ProgrammingL-BAL-E057-GB 1304 Index 009 Part.-No. 00163327-GB46/74