Switch over between “Setpoint1” and “Setpoint2” (for modes as controller higher 3.10 )Contact at digital input e.g. “Digital In 1”.Controller10n = 0 – 100 %- - - - -- - - - -Sensor27.11.2008v_5d_sollwert_1_2_m.vsd12D1 D1M1 Setting “Setpoint1”2 Setting “Setpoint2”• “D1 Inverting” = “OFF”: “Setpoint1” =18 °C at opened contact / “Setpoint2” =25 °C at closed contact.• “D1 Inverting” = “ON”: “Setpoint1” = 18°C at closed contact / “Setpoint2” = 25°C at opened contact.E1 ActualOperation with “Setpoint2” is signalized by the moon symbol for reduced operation.9.6.2.7 Intern / Extern Function |6D|Switch over between Set Intern and Set Extern (for mode speed controller 1.10 ... 1.11 ). “Setextern1” under settings must be programmed to “OFF”.Contact at digital input e.g. “Digital In 1”.ControllerD1 D110n = 40 %n = 80 %Si 40 %- - - - -E127.11.2008v_6d_vorgabe_intern_extern_m.vsd10 MSi Signal1 Setting “Set Intern1” (depending on device type in: %, Hz, rpm)• “D1 Inverting” = “OFF”: “Set Intern1” atopened contact / “Setting Extern” atclosed contact.• “D1 Inverting” = “ON”: “Set Intern1” atclosed contact / “Set Extern” at openedcontact.“Setpoint1” / “external Setpoint” (modes 3.10 )Under Base setup “E2 function” programmed to function |1E| for “external setpoint” .Contact at digital input e.g. “Digital In 1” = “D1” - “D1”ControllerD1 D110n = 0 – 100 %- - - - -SeES E227.11.2008v_6d_sollwert1_externer_sollwert_m.vsd1M1 Setting “Setpoint1”ES External Setpoint e.g. 5 VSe Sensor• “D1 Inverting” = “ON”: Setting at the unitat opened contact / Signal Extern atclosed contact• “D1 Inverting” = “OFF”: Setting at theunit at closed contact / Signal Extern atopened contactOperating Instructions Fcontrol – model series FKDM..-C ProgrammingL-BAL-E057-GB 1304 Index 009 Part.-No. 00163327-GB47/74