All rights reserved Side 5 af 16Input.T9_Heater 209 100 °C Heating surface temperature VPL-VPM-Comfort-ComfortiInput.T10_Extern 210 100 °C External room temperature All plantsInput.T11_Top 211 100 °C Hot water top temperature VGU-VP-CompactInput.T12_Bottom 212 100 °C Hot water bottom temperature VGU-VP-CompactInput.T13_Return 213 100 °C EK return temperature VGU-VPInput.T14_Supply 214 100 °C EK supply temperature VGU-VPInput.T15_Room 215 100 °C User panel room temperature All plantsInput.T16 216 100 °C AUX temperature (sacrificialanode)VGU-VP-CompactInput.T17 217 100 °C Preheater or earth tube airintake temperature-- 218..220 (reserved)Input.RH 221 100 % Humidity All plantsInput.CO2 222 ppm Carbon dioxide All plantsAlarm.Status 400 Alarm state bit mask0x80 : Active alarm(s) present0x03 : Nb. of alarms listedAllAlarm.List_1_ID 401 Alarm 1 – Code0x80 : (reserved future use)0x7F : Display code 1..99AllAlarm.List_1_Date 402 Alarm 1 – DateBit word packed in DOS dateformat. Year 0 = 198015 8 7 0HHHHHMMM MMMSSSSSAllAlarm.List_1_Time 403 Alarm 1 – TimeBit word packed in DOS timeformat. Seconds are in scale 2(0..29=0..58 seconds)15 8 7 0HHHHHMMM MMMSSSSSAllAlarm.List_2_ID 404 Alarm 2 - Code AllAlarm.List_2_Date 405 Alarm 2 - Date AllAlarm.List_2_Time 406 Alarm 2 - Time AllAlarm.List_3_ID 407 Alarm 3 - Code AllAlarm.List_3_Date 408 Alarm 3 - Date AllAlarm.List_3_Time 409 Alarm 3 - Time AllControl.RunAct 1000 Actual on/off state0 : Off1 : OnAllControl.ModeAct 1001 Actual operation mode0 : Off1 : Heat2 : Cool3 : Auto4 : ServiceAll