All rights reserved Side 6 af 16Control.State 1002 Actual control state0 : Off1 : Shift2 : Stop3 : Start4 : Standby5 : Ventilation stop6 : Ventilation7 : Heating8 : Cooling9 : Hot water10 : Legionella11 : Cooling + hot water12 : Central heating13 : Defrost14 : Frost secure15 : Service16 : Alarm17: Heating + hot waterAllControl.SecInState 1003 Sec Actual time in state AllAirFlow.VentSet 1100 Step Actual ventilation step set point0 : Off1..4 : Step numberAllAirFlow.InletAct 1101 Step Actual ventilation step set point0 : Off1..4 : Step numberAllAirFlow.ExhaustAct 1102 Step Actual ventilation step set point0 : Off1..4 : Step numberAllAirFlow.SinceFiltDay 1103 Days Days since last air filterchange alarmOne day is measured as 24hours of active running timeAllAirFlow.ToFiltDay 1104 Days Days to next air filter changealarmOne day is measured as 24hours of active running timeAllAirTemp.IsSummer 1200 Summer state0 : Off1 : OnAllAirTemp.TempInletSet1201 100 °C Inlet temperature request (T7setpoint)AllAirTemp.TempControl1202 100 °C Actual value for controlledtemperatureAllAirTemp.TempRoom 1203 100 °C Actual room temperature (T15or T10)AllAirTemp.EffPct 1204 100 % Passive heat exchangerefficiencyCompact-Comfort-ComfortiAirTemp.CapSet 1205 100 % Requested capacity All plantsAirTemp.CapAct 1206 100 % Actual capacity All plants