May be subject to change page 18 af 33Central heatingSettings for boiler control are displayed in the CENTRAL HEATING menu. The values shown arerecommended values.Options that flash are indicated by ” ”.CENTRALHEATINGMODEHEATMODE”OFF”MODE”HEAT”ENTER ENTERENTERENTERSUPPLYMIN 25°CSUPPLYMAX 40°CENTERMODE”DEMAND”Can be set from 5 – 40°CCURVE5OFFSETCUR 0°COFFSETT15 0°CDELAY0 MINPUMPENERGYENTER PUMP”ENERGY”PUMP”CONTIN”Can be set from 25 – 85°CCan be set from 0 – 2°CCan be set from 1 -10°CCan be set from -15 -10°CCan be set from 0 – 30minuttes”DEMAND” will stop the EK-module when there is a highpressure alarmOnly avaiable whenMODE DEMAND hasbeen selected.Figure 12: The "Central heating" menu