User select 2ENTERENTERENTERENTERSELECTEXTENDTIME00:00FLOW>4<TEMP23°CTIME”00:00”FLOW”>4<”TEMP”23°C”ENTER ENTER SELECT”EXHAUST”SELECT”EXT OFFS”SELECT”VENTILAT”SELECT”C HOOD”ENTERENTERENTER SELECT”OFF”SELECT”EXTEND”USERSELECT 2ENTERENTER123SELECT”INLET”576481. TIME 00:00 Required period in which the selected function is to remainoperative, started in hours and minutes. Max. 8 hours.2. FLOW <4> Required ventilation level : 1-4. OFF allows the system to be shutdown via an external switch.3. TEMP 23°C Required room temperature (5-30°C). Panel sensor T15 is thecontrolling sensor.4. SELECT "INTAKE" "EXHAUST" Time and speed must be set in the same way, as described underSELECT EXTEND.5. SELECT "EX OFFS" Option for relay output R8, if fitted. Only possible on asupplementary PCB. The temperature is added or subtracted to/from the set point. Choose the afterrunning and displacement ofthe set point for external room heating. Selected in the same wayas shown under SELECT EXTEND .6. SELECT "VENTILAT" Possibility to run a higher or lower spped. High priority.7. SELECT "C HOOD" RE7: Close switch for controlling of hood damper motor.8. SELECT "OFF" User selection deactivated.The USER SELECT 2 menu is used as USER SELECT . (only shown when option PCB is fitted)Comfort 200 Top (English) BY NILAN13