IMPORTANT, concerning Danfoss Actuator type AME 140:Mandatory procedure for refitting the actuator:1. Disconnect from mains electricity. Remove actuator cover.2. Disengage the gear by holding the button under the housing in while screwing the spindle upwardsas far as it will go (counter-clockwise)3. Fit actuator and reconnect mains electricity.4. Switch DIP switch no. 1 to ON and then OFF.5. Automatic calibration will run for up to 6 minutes.(The diode will flash during calibration before becoming constant).6. Fit actuator cover.Output chart, hot water heaterWater side Air side[°C] [m3 /h] [kPa] [kW] [m 3 /h] [°C] [°C] [Pa]40/300,04 0,85 0,52 100 16 31,1 20,06 1,25 0,64 135 16 29,8 30,08 2,18 0,87 210 16 28,1 60,11 4,65 1,32 400 16 25,7 170,17 9,62 1,98 800 16 23,2 530,19 11,9 2,23 1000 16 22,5 7760/400,04 0,69 0,94 100 16 43,5 20,05 1,00 1,16 135 16 41,1 30,07 1,75 1,58 210 16 38,0 60,10 3,70 2,40 400 16 33,5 170,16 7,66 3,58 800 16 29,1 530,18 9,48 4,03 1000 16 27,8 7770/400,03 0,40 1,06 100 16 47,0 20,04 0,58 1,30 135 16 44,2 30,05 1,00 1,76 210 16 40,5 60,08 2,09 2,64 400 16 35,3 170,11 4,25 3,9 800 16 30,3 530,13 5,24 4,38 1000 16 28,8 77Temperaturesupply/returnFlow Pressure loss Output Air volume Temperaturebefore HWH*Temperatureafter HWH*Pressure lossover HWH**(HWH) hot water heaterCompact P / Compact P Polar - GEO (English) BY NILAN45