9.2 Adding setting groupsIn order to show for a DNP master which setting group is used, the followingprocedure can be performed.In this example, only setting groups one and two are used. The DNP master willget two binary inputs: the first is set if setting group one is used, the second is set ifsetting group two is used.1. Configure ACTVGRP (Basic IED functions) and SP16GGIO (Monitoring)with the Application Configuration Tool (ACT).IEC11000423-1-en.vsdIEC11000423 V1 ENFigure 72: Application configuration toolTo make it easier to recognize the signals for the active settinggroup, the user-defined names are used.2. Open the Communication Management Tool (CMT). Set the Signal Type toBinary Input Object and choose the connection of the master for which thevalues should be presented.Section 9 1MRK 511 261-UEN -DNP3 communication engineering104 650 seriesEngineering Manual