Linearization FCM Appendix A Runtime Templates260 3BUR002418-600 ALO ENG UNITS Field (Low Engineering Units)This field specifies the low limit of the engineering units range. Valid entry is anynumber.Linearization FCMThis FCM uses the table look-up method to linearize an input. The linearizationtables support thermocouples and RTDs (Resistance Temperature Devices) used bythe system. As an option, the FCM can linearize according to a table defined by youvia the Breakpoint Sets Templet. The result of this FCM is scaled in degrees C(Celsius), F (Fahrenheit), K (Kelvin), or R (Rankine).INVERSE AXIS? FieldThis field specifies either normal or inverted axis. Valid entries are:NO do not invert axis (input value is the x value in the linearizationtable, corresponding y value becomes the result)YES invert axis (input value is the y value in the linearization table,corresponding x value becomes the result)Normalize FCMThe Normalize FCM normalizes a signal from an engineering unit scale to adimensionless zero-based scale.LOW RANGE FieldThis field specifies the low range value for the input signal. Valid entry is anynumber.HIGH RANGE FieldThis field specifies the top of range value for engineering units range of the result.Valid entry is any number.