Section 4 TCL Displays Sequence Detail Display Format3BUR002418-600 A 85Sequence Detail Display FormatThe unit ID, recipe ID, batch ID, and sequence are shown at the top of the SequenceDetail Display. Step data fields show the current step, next step, step time (the timespent executing the current step), and pause step (or the step on which the programpauses in semiauto mode). There are also fields that show the current state, mode,priority, and status. The Display Steps field lists the sequence steps in numericalorder, with the currently executing step highlighted.Choosing a Sequence for Sequence DetailDirect access of a sequence detail is possible from the MOD_SEQUENCE objectwhich specifies a valid sequence as defined during configuration. Otherwise, alisting of TCL sequences is provided when you first enter a MOD Sequence Detaildisplay from a MOD_UNIT object. Choose the sequence to be loaded from the liston the Sequence List display, Figure 35.Changing Sequence State, Mode, and StatusTo change state, mode, or status, use the pull-down list and make your selection.Manipulating Sequence StepsSequence steps can be operated manually one at a time or semi-automatically. Stepscan be skipped and they can also be repeated. To make step changes, first select thestep, and then enter the new values in the Next Step and Pause Step boxes. Next StepFigure 35. TCL Sequence List