Flow Calculation FCM Appendix A Runtime Templates262 3BUR002418-600 ANEW HIGH RANGE FieldThis field specifies high range value of the result. Valid entry is any number.Flow Calculation FCMThis FCM calculates mass and volume flow rates for liquids and gases. Its primaryinput is either a differential pressure measurement or a velocity measurement.STANDARD TEMP FieldThis field specifies the standard temperature. Temperature must be absolute(degrees Rankine). Valid entry is any number.FLOWING TEMP FieldThis field specifies the flow temperature. It is used when TEMP LOC/REM isLOCAL. The temperature must be absolute (deg. Rankine where deg. Rankine =deg. Fahrenheit + 459.69). Valid entry is any number greater than 0.FLOWING PRESSURE FieldThis field specifies the flow pressure. It is used when PRES LOC/REM is LOCAL.Valid entry is any number greater than 0. The entry must be in PSIA.FLOWING DENSITY FieldThis field specifies the flow density. It is used when DEN LOC/REM is LOCAL.Valid entry is any number greater than 0.DENSITY SC FieldThis field specifies the value for the density at standard conditions. Valid entry isany number.SPEC GRAV SC FieldThis field specifies the value for specific gravity at standard conditions. Valid entryis any number.