3.4.6 ParameterizationThe arrangement of the parameter data is performed by your system configuration software PS501 ControlBuilder Plus V2.2.1 (or newer) / ABB Automation Builder 1.0 (or newer). ABB GSDML file for PROFINETdevices can be used to configure DX581-S parameters in 3rd party PROFINET F-Host systems.The parameter setting directly influences the functionality of modules and reachable SIL (IEC 61508 ed. 2and IEC 62061) and PL (ISO 13849).No. Name Values Default1 Check supply “On”, “Off” “On”Inputs2 Input channel Con-figuration“Not used”, “1 channel”, “2 channel equivalent”, “2channel antivalent”“Not used”3 Test pulse “Disabled”, “Enabled” “Disabled”4 Input delay “1 ms”, “2 ms”, “5 ms”, “10 ms”, “15 ms”, “30 ms”,“50 ms”, “100 ms”, “200 ms”, “500 ms”“5 ms”5 Discrepancy time* “10 ms”, “20 ms”, “30 ms”, “40 ms”, “50 ms”,“60 ms”, “70 ms”, “80 ms”, “90 ms”, “100 ms”,“150 ms”, “200 ms”, “250 ms”, “300 ms”, “400 ms”,“500 ms”, “750 ms”, “1 s”, “2 s”, “3 s”, “4 s”, “5 s”,“10 s”, “20 s”, “30 s”“50 ms”Outputs6 Output channel con-figuration“Not used”, “Used” “Not used”7 Detection (internaloutput channel test)“Off”, “On” “On”* Available only for “2 channel equivalent” and “2 channel antivalent” configuration3.4.7 Circuit examplesExamples of electrical connections and reachable SIL (CL) (IEC 61508 ed. 2 and IEC 62061), PL (ISO13849) and Category (EN 954) with DX581-S module are presented below. Note, that electrical connectionspresented for DI581-S safety input channels are also valid for DX581-S safety input channels.NOTICE!Whenever DC = High is used in the circuit examples for safety digital inputs, the following measurefrom ISO 13849-1 [10] is used in DX581-S module: Cross monitoring of input signals and intermediateresults within the logic (L), and temporal and logical software monitor of the program flow and detec-tion of static faults and short circuits (for multiple I/O).Whenever DC = Medium is used in the circuit examples for safety digital inputs, any of the measuresfor input devices with DC ³ 90 % can be used from ISO 13849-1 [10].AC500-S Safety ModulesDX581-S digital safety input/output module > Circuit examples30.03.2017 AC500-S 117