Program features132ExampleAir conditioning is active on weekdays from 8:00 to 15:30 (8 a.m to 3:30 p.m) and onSundays from 12:00 to 15:00 (12 to 3 p.m). By pressing the extension time switch,the air-conditioning is on for an extra hour.SettingsTimerDrive start and stop can be controlled with timer functions.SettingsDiagnosticsParameter Setting3602 START TIME 1 08:00:003603 STOP TIME 1 15:30:003604 START DAY 1 MONDAY3605 STOP DAY 1 FRIDAY3606 START TIME 2 12:00:003607 STOP TIME 2 15:00:003608 START DAY 2 SUNDAY3609 STOP DAY 2 SUNDAY3623 BOOSTER TIME 01:00:00Parameter Additional information36 TIMED FUNCTIONS Timed functions settings1001, 1002 Timed start/stop control1102 Timed EXT1/EXT2 selection1201 Timed constant speed 1 activation1209 Timed speed selection1401 Timed function status indicated through relay output RO1805 Timed function status indicated through digital output DO4027 Timed PID1 parameter set 1/2 selection4228 Timed external PID2 activation8402 Timed sequence programming activation8425/8435/.../84958426/8436/.../8496Sequence programming state change trigger with timed functionParameter Additional information1001, 1002 Start/Stop signal sources19 TIMER & COUNTER Timer for start and stopActual value Additional information0165 Start/stop control time count