Guidelines for planning the electrical installation 87A diagram of the cable routing is shown below. Separate control cable ductsLead 24 V and 230 V (120 V) control cables in separate ducts unless the 24 V cable isinsulated for 230 V (120 V) or insulated with an insulation sleeving for 230 V (120 V). Continuous motor cable shield or enclosure for equipment on themotor cableTo minimize the emission level when safety switches, contactors, connection boxes orsimilar equipment are installed on the motor cable between the drive and the motor:• European Union: Install the equipment in a metal enclosure with 360 degreegrounding for the shields of both the incoming and outgoing cable, or connect theshields of the cables otherwise together.• US: Install the equipment in a metal enclosure in a way that the conduit or motor cableshielding runs consistently without breaks from the drive to the motor.90 ° min 500 mm (20 in.)min 200 mm (8 in.)min 300 mm (12 in.)DriveMotor cablePower cableMotor cableInput power cableControl cables24 V 24 V230 V(120 V)230 V(120 V)