Parameters 131154154 FBA B settings Fieldbus adapter B configuration.154.01 FBA B type Displays the type of the connected fieldbus adapter module.0 = Module is not found or is not properly connected, or isdisabled by parameter 150.31 FBA B Enable; 1 = FPBA;32 = FCAN; 37 = FDNA; 101 = FCNA; 128 = FENA-11/21;132 = PROFINET IO; 135 = FECA; 136 = FEPL;485 = FSCA; 62944 = FSEA.Note: All types of the fieldbus adapter modules are notnecessarily supported yet.This parameter is read-only.-154.02 FBA B Par2 Parameters 154.02…154.26 are adapter module-specific.For more information, see the documentation of the fieldbusadapter module. Note that not all of these parameters arenecessarily used.-0…65535 Fieldbus adapter configuration parameter. 1 = 1… … … …154.26 FBA B Par26 See parameter 154.26 FBA B Par2. -0…65535 Fieldbus adapter configuration parameter. 1 = 1154.27 FBA B par refresh Validates any changed fieldbus adapter moduleconfiguration settings. After refreshing, the value revertsautomatically to Done.Note: This parameter cannot be changed while the DC/DCconverter unit is running.DoneDone Refreshing done. 0Configure Refreshing. 1154.28 FBA B par table ver Displays the parameter table revision of the fieldbus adaptermodule mapping file stored in the memory.In format axyz, where a = major revision number; xy = minorrevision number; z = correction number.-Parameter table revision of adapter module. 1 = 1154.29 FBA B drive typecodeDisplays the type code of the fieldbus adapter modulemapping file stored in the memory.-0…65535 Type code of fieldbus adapter module mapping file. 1 = 1154.30 FBA B mapping fileverDisplays the fieldbus adapter module mapping file revisionstored in the memory of the DC/DC converter unit indecimal format.Example: Integer 263 -> 0x107 = revision 1.07-0…65535 Mapping file revision. 1 = 1154.31 D2FBA B comm sta Displays the status of the fieldbus adapter modulecommunication.IdleIdle Adapter is not configured. 0Exec.init Adapter is initializing. 1Time out A time-out has occurred in the communication between theadapter and the DC/DC converter unit.2Conf.err Adapter configuration error: the major or minor revisioncode of the common program revision in the fieldbusadapter module is not the revision required by the module(see parameter 154.32 FBA B comm SW ver), or mappingfile upload has failed more than three times.3Off-line Adapter is off-line. 4On-line Adapter is on-line. 5Reset Adapter is performing a hardware reset. 6No. Name/Value Description Def/FbEq16