Wiring with the display system2281SVC 440 795 M1100Example 1:The source range is a 10-bit value, source is the analog inputIA01.The target range has 12 bits.Parameter display and parameter set for the LS01 functionblock:The actual value at the analog input IA01 is 511.The scaled output value is 2045.Example 2:The source range has 12 bits.The target range has 16 signed bits.>I1 = DC01QV>X1 = 0>X2 = 4095>Y1 = –32768>Y2 = +32767The actual value at the analog input DC01QV is 1789.The scaled output value is –4137.JumpsJumps can be used to optimise the structure of a circuitdiagram or to implement the function of a selector switch.Jumps can be used for example to select whether manual/automatic operation or other machine programs are to be set.Jumps consist of a jump location and a jump destination(label).LS01 +>I1 IA01>X1 0>Y1 0>X2 1023>Y2 4095QV>