Table 45:General settings parameters for the Measurement functionSetting Short description SelectedvalueCommentOperation Operation Off/On On Function must beOnPowAmpFact Amplitude factor to scale powercalculations1.000 Typically no scaling is requiredPowAngComp Angle compensation for phaseshift between measured I & V0.0 Typically no angle compensation isrequired. As well here requireddirection of P & Q measurement istowards protected object (as per IEDinternal default direction)Mode Selection of measured currentand voltageArone Generator VTs are connected betweenphases (V-connected)k Low pass filter coefficient forpower measurement, V and I0.00 Typically no additional filtering isrequiredVGenZeroDb Zero point clamping in % ofVbase25% Set minimum voltage level to 25%IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%VBase (set inGlobal base)Base setting for voltage level inkV15,65 Set generator rated phase-to-phasevoltageIBase (set inGlobal base)Base setting for current level in A 3690 Set generator rated current14.2 Gas medium supervision SSIMG (63)14.2.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberGas medium supervision SSIMG - 6314.2.2 ApplicationGas medium supervision (SSIMG ,63) is used for monitoring the circuit breakercondition. Proper arc extinction by the compressed gas in the circuit breaker is veryimportant. When the pressure becomes too low compared to the required value, the circuitbreaker operation shall be blocked to minimize the risk of internal failure. Binaryinformation based on the gas pressure in the circuit breaker is used as an input signal to thefunction. The function generates alarms based on the received information.Section 14 1MRK 505 337-UUS -Monitoring414Application manual