16.2.4.1 ApplicationGeneric communication function for Measured Value (SPGAPC) function is used to sendone single logical output to other systems or equipment in the substation. It has one visibleinput, that should be connected in ACT tool.16.2.4.2 Setting guidelinesThere are no settings available for the user for SPGAPC. However, PCM600 must be usedto get the signals sent by SPGAPC.16.2.5 Generic communication function for Measured Value MVGAPC16.2.5.1 ApplicationGeneric communication function for Measured Value MVGAPC function is used to sendthe instantaneous value of an analog signal to other systems or equipment in thesubstation. It can also be used inside the same IED, to attach a RANGE aspect to an analogvalue and to permit measurement supervision on that value.16.2.5.2 Setting guidelinesThe settings available for Generic communication function for Measured Value(MVGAPC) function allows the user to choose a deadband and a zero deadband for themonitored signal. Values within the zero deadband are considered as zero.The high and low limit settings provides limits for the high-high-, high, normal, low andlow-low ranges of the measured value. The actual range of the measured value is shownon the range output of MVGAPC function block. When a Measured value expander block(RANGE_XP) is connected to the range output, the logical outputs of the RANGE_XP arechanged accordingly.16.2.6 IEC 61850-8-1 redundant station bus communication16.2.6.1 IdentificationFunction description LHMI and ACTidentificationIEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberParallel RedundancyProtocol StatusPRPSTATUS RCHLCCH - -Duo driverconfigurationPRP - - -Section 16 1MRK 505 337-UUS -Station communication438Application manual