9.2.6 Control9.2.6.1 Apparatus controlOverviewUnder Control in General settings, parameters for Apparatus control can beadjusted. These are the parameters for among others Bay control, Switch controller,Reservation input, Circuit breakers and Circuit switches. The parameters includedelay times, dependencies, pulse times and characteristics.Bay control QCBAYMain menu/Settings/General settings/Control/ApparatusControl/BayControl(CBAY)/QCBAY:xDisplays up to six instances of the bay control function QCBAY with a setting thatgives the local operator priority over the remote operator or vice versa.Bay reserve QCRSVMain menu/Settings/General settings/Control/ApparatusControl/BayReserve(CRSV)/QCRSV:xDisplays up to four instances of the bay reserve function QCRSV with nineparameter settings. The first is for setting the supervision time to cancel areservation and the other eight are for the reservation of the own bay only at theselection of an apparatus.Circuit breaker SXCBRMain menu/Settings/General settings/Control/ApparatusControl/CircuitBreaker(XCBR)/SXCBR:xDisplays available instances of the circuit breaker function with parameter settingsSXCBR for various time limits and pulse lengths. For example, different circuitbreakers may require different pulse lengths to react. The setting tOpenPulse isused to set the length of the pulse required to open a breaker.Circuit switch SXSWIMain menu/Settings/General settings/Control/ApparatusControl/CircuitSwitch(XSWI)/SXSWI:xDisplays available instances of the circuit switch function SXSWI with a numberof settable parameters per instance for time and pulse settings, output reset andswitch type.Local/Remote switch LocalRemote, LocRemControlMain menu/Settings/General settings/Control/ApparatusControl/LocalRemote/LOCREM:xSection 9 1MRK505209-UEN ERead and change settings50Operator's manual