6.2.2 Application GUID-8DF29209-252A-4E51-9F4A-B14B669E71AB v4The phasor measurement reporting block moves the phasor calculations into an IEEEC37.118 and/or IEEE 1344 synchrophasor frame format. The PMUREPORT blockcontains parameters for PMU performance class and reporting rate, the IDCODE andGlobal PMU ID, format of the data streamed through the protocol, the type of reportedsynchrophasors, as well as settings for reporting analog and digital signals.The message generated by the PMUREPORT function block is set in accordance withthe IEEE C37.118 and/or IEEE 1344 standards.There are settings for Phasor type (positive sequence, negative sequence or zerosequence in case of 3-phase phasor and A, B or C in case of single phase phasor),PMU's Service class (Protection or Measurement), Phasor representation (polar orrectangular) and the data types for phasor data, analog data and frequency data.Synchrophasor data can be reported to up to 8 clients over TCP and/or 6 UDP groupclients for multicast or unicast transmission of phasor data from the IED. Moreinformation regarding synchrophasor communication structure and TCP/UDPconfiguration is available in section C37.118 Phasor Measurement Data StreamingProtocol Configuration.Multiple PMU functionality can be configured in the IED, which can stream out sameor different data at different reporting rates or different performance (service) classes.There are 2 instances of PMU functionality available in the IED. Each instance ofPMU functionality includes a set of PMU reporting function blocks tagged by the sameinstance number (1 or 2). As shown in the following figures, each set of PMUreporting function blocks includes PMUREPORT, PHASORREPORT1-4,ANALOGREPORT1-3, and BINARYREPORT1-3 function blocks. In general, eachinstance of PMU functionality has 32 configurable phasor channels(PHASORREPORT1–4 blocks), 24 analog channels (ANALOGREPORT1-3 blocks),and 28 digital channels (24 digital-report channels in BINARYREPORT1-3 and 4trigger-report channels in PMUREPORT function block). Special rules shall be takeninto account in PCM600 for Application Configuration and Parameter Settings ofmultiple PMUREPORT blocks. These rules are explained in the the ApplicationManual in section PMU Report Function Blocks Connection Rules.Figure 33 shows both instances of the PMUREPORT function block. As seen, eachPMUREPORT instance has 4 predefined binary input signals corresponding to the Bits03-00: Trigger Reason defined in STAT field of the Data frame in IEEE C37.118.2standard. These are predefined inputs for Frequency Trigger, Rate of Change ofFrequency trigger, Magnitude High and Magnitude Low triggers.Section 6 1MRK 511 401-UUS AWide area measurement system106 Bay control REC670 2.2 ANSIApplication manual